Page 40 of 40
FIRElink-100 – Installation Manual
©
2010 Hochiki Europe (UK) Ltd
9-5-0-345/ISS4/OCT10
10 FIRElink-100 Specification
SELV Rating (EN 60950)
Class III
Supply Voltage
21.6Vd.c. - 26.4Vd.c.
PSU Type: conforming to EN 54-4 Electrical safety complies with
BS EN 610190-1
Size (mm)
300W x 220H x 85D
Weight
3.8kg with docking station
Operating Temperature Range
0 to +38°C (UL268)
-10 to +60°C (CEA4022)
Operating Humidity Range
0 - 90% Non Condensing
BS EN 61010-1 Pollution degree 1
BS EN 61010-1 Installation Cat. II
0.03% to 25% Full Scale Deflection (FSD)
Measurement Range (obs/m)
0.0015% to 25% Sensitivity Resolution
Detection Principle
Laser light scattering mass detection
Particle Sensitivity Range
0.0003µm to 10µm
Current Consumption
400mA @ 24Vd.c.
Relay Contact Rating
500mA @ 30Vd.c.
Maximum Sampling Pipe Length
100 metres total (see section 2 "Design Limitations" on page 20)
Sampling Pipe Inlets
2
Sampling Pipe Internal Diameter
15-25mm
Alarm levels
2 – "FIRE" and "FAULT" (2 additional levels available with
optional Relay Card or FIRElink-APIC fitted)
Chamber Service Intervals
Greater than 8 years (depending on environment)
Dust Separator Replacement Intervals Greater than 5 years (depending on environment)
Laser Lifetime (MTTF)
Greater than 1000 years
Programming PC
via
RS232/RS485
Data Bus Cable
RS485 data cable
Data Bus Length
1.2 km
IP Rating
IP50
NOTE: This equipment is only to be used in accordance with this specification. Failure to operate the
equipment as specified may cause damage to the unit.