ESP FIREbeam – Installation Manual  

 

Page 15 of 19 

 2011 Hochiki Europe (UK) Ltd 

2-3-0-1340/ISS2/DEC11 

    

 

 

3.3.3 

Mode Change  

Here we can make changes to how the beam behaves.  Press 

enter

 to 

go into the ‘Mode Change’ menu and access the sub menus. 

Threshold

 - use the 

right

 and 

left

 keys to increase or decrease 

the beams sensitivity.  It is factory set at 35% (meaning the received 
signal has to drop by 35% to trigger the fire relay.  This sensitivity can be 
adjusted between 25% (sensitive) and 50% (less sensitive).  Press 

enter

 to return to ‘Mode Change’ or 

down

 to go to ‘Time to Fire’. 

Time to Fire

 - you can adjust how long the beam has to be in fire 

before the fire relay is triggered.  This is factory set at 10s, you may want 
to increase this if there is something that may momentarily obscure the 
beam path (birds/forklift truck etc).  This can be adjusted between 2 and 
30 seconds by using the 

right

 and 

left

 keys.  Press 

enter

 to 

return to ‘Mode Change’ or 

down

 to go to ‘Time to Fault’. 

Time to Fault

 - you can adjust the time to fault between 2 and 60 

seconds (factory set at 10 seconds).  For a beam to go into fault the 
beam path must be totally blocked within ONE second.  By using the 

right

 and 

left

 keys.  Press 

enter

 to return to ‘Mode Change’ or 

down

 to go to ‘Auto Reset’). 

Auto Reset

 - the beam is factory set to auto reset when the received 

signal raises above the fire threshold hysteresis.  This can be set to 
latching if your system requires this.  Change by using the 

right

 and 

left

 keys.  Press 

enter

 to return to ‘Mode Change’ or 

down

 to go to 

‘Align On/Off’. 

Align On/Off

 - you may want to turn the auto alignment function off, for 

example, in an environment that often gets filled with welding smoke, the 
auto align function kicks in when the received signal drops below 90%, 
the point that the beam automatically checks for building movement.  The 
beam will try to align through the smoke which could be a problem if it is 
unable to see the edges of the reflector.  Use the 

right

 and 

left

 keys 

to turn off and on.  When turning this function off extra care should be 
taken to ensure that the beam head is on a sturdy fixing, in other words, 
a brick wall or major structural steel.  Auto alignment will still function in 
commissioning.  Press 

enter

 to return to ‘Mode Change’ or 

down

 to go 

to ‘Align Time’. 

Align Time

 - this is factory set to 4hrs, you can adjust this, by using the 

right

 and 

left

 keys, between 0 to 12 hours depending on your 

environment.  Press 

enter

 to return to ‘Mode Change’ or 

down

 to go to 

‘Green Flashing Light On/Off’. 

Green Flashing Light On/Off

 - you can turn the green flashing LED, 

located on the head and controller, on or off using the 

right

 and 

left

 

keys.  This is a useful way of identifying the beam head you are working 
with.  Press 

enter

 to return to ‘Mode Change’ or 

down

 to go to ‘Phase’. 

 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for ESP FIREbeam

Page 1: ...esp FIREbeam INSTALLATION MANUAL www acornfiresecurity com www acornfiresecurity com...

Page 2: ...www acornfiresecurity com www acornfiresecurity com...

Page 3: ...2 Step 2 Programming the Analogue Address 6 2 3 Step 3 Mounting the Controller 7 2 4 Wiring Configuration 7 2 5 Step 4 Commissioning 8 2 5 1 Stage One Language and Commissioning Speed 8 2 5 2 Stage T...

Page 4: ...ESP FIREbeam comes boxed with the head unit low level controller one reflector 3mm allen key and quick start installation guide this should be used for distances over 5m and up to 40m 1 1 2 40 to 80 m...

Page 5: ...40m from the floor The maximum protected area either side of the beam can be extended by 1 for every degree of roof pitch see the example below NOTE Careful design consideration should be made when p...

Page 6: ...the front edge of the box Wire to low level controller using bottom colour coded terminals Screw in through holes provided outside of the rubber seal 2 2 Step 2 Programming the Analogue Address The F...

Page 7: ...this connection can be checked by reading the resistance across the black and grey terminals they will read 110 ohm if OK or 220 ohm if not connected properly 2 4 Wiring Configuration The output curre...

Page 8: ...in normal mode the system uses 3 5mA in fast mode it uses 17mA if you are commissioning more than one beam at a time and the system cannot support the extra draw it may be necessary to use normal mod...

Page 9: ...ng noticeably less read on below These figures are approximate but if you are receiving noticeably less than these figures you may be receiving a reflection from an object nearby and not the far wall...

Page 10: ...higher the AQ the quicker it will auto align This is done by manually moving the x and y motors to obtain a received signal from the reflector In the example below we can see that the reflector is bel...

Page 11: ...low 100 Now proceed to Step 4 Testing the final stage of commissioning 2 6 Step 5 Testing 2 6 1 Fault Test This is done to confirm that the returned signal is from the reflector Cover the entire refle...

Page 12: ...it will reset to normal automatically FAULT The beam path has been fully blocked within 1 second used when fault testing in commissioning ERROR No communication with the controller This could be that...

Page 13: ...ress down to go through the main menu options Select this option to change system language Select this option to commission the ESP FIREbeam Select this option to make all changes and adjustments to t...

Page 14: ...automatically stop when a received signal strength reaches 6 this received signal is the returned strength of the output signal without a reflector if no return signal is received the beam will reach...

Page 15: ...ved signal raises above the fire threshold hysteresis This can be set to latching if your system requires this Change by using the right and left keys Press enter to return to Mode Change or down to g...

Page 16: ...enter to return to Mode Change or down to go to Hysteresis Hysteresis Changing the hysteresis will change the delay in returning from a fire state back to a normal state For example the beam is facto...

Page 17: ...to Beam Maintenance or down to go to Alarm Fault Event Counts Alarm Fault Event Counts Here we can see how many times the beam has gone into fire or fault since the beam was commissioned or since the...

Page 18: ...t and left keys Press enter to return to Diagnostics or down to go to RX Sensitivity RX Sensitivity This screen shows the receiver sensitivity and can be changed by using the right and left keys Press...

Page 19: ...larm Condition adjustable 2 to 30 seconds in 1 second increments default 10 seconds Alarm Indication Controller Status FIRE Controller Red Flashing LED Head Red Flashing LED Alarm Relay Change Over CO...

Reviews: