background image

ESP FIREbeam – Installation Manual  

 

Page 11 of 19 

 2011 Hochiki Europe (UK) Ltd 

2-3-0-1340/ISS2/DEC11 

    

 

2.5.4 

Stage Four - Auto-Alignment 

Having received an AQ reading of over 40% in manual mode press enter to exit manual and enter again to go into 
auto alignment mode. 

 

First you will see the sensitivity and power readings drop if the received signal is over 100%.  Once at 100% or if 
the reading is under 100% the ESP FIREbeam will automatically move its y and x axis until it centres itself onto the 
middle of the reflector.  It does this by seeing highs and lows as it falls on and off the reflector (seeing the edges of 
the reflector) once it has found all the edges it will then calculate and move to the centre of the reflector. 

 

 

Auto alignment in ‘fast’ mode will take, on average, 3 minutes and in normal mode up to 30 minutes; the better the 
beam is aligned before auto alignment (high AQ readings) the shorter the align time.  Once finished 

Align 

Complete

 will appear on the screen, simply press 

left

 to get back to OK and exit. 

You will now see this screen, AQ may fluctuate a couple of % above and below 100%  

 

Now proceed to Step 4 – Testing, the final stage of commissioning. 

2.6  Step 5 - Testing 

2.6.1 Fault 

Test 

 

This is done to confirm that the returned signal is from the reflector.  Cover the entire reflector within one second.  If 
the beam is correctly targeted onto the reflector the AQ will drop to 0% (max 10%) and will fall into a ‘fault’ condition 
(after 10 seconds).  Amber LEDs will flash on the controller and the beam head, the word 

FAULT

 will appear on 

the display.  If the AQ is still above 10% reflections are also being returned from something else other than the 
reflector.  This should be rectified and a fault test performed again until AQ drops below 10%. 

2.6.2 Fire 

Test 

 

Having completed the fault test the fire test confirms the functionality of the beam.  Having just covered the reflector 
completely for the fault test now let the beam recover to its normal state and then cover half the reflector, in effect 
restricting the returned signal to 50%, the beam should then fall into a ‘fire’ condition (after 10 seconds). 

Once you have successfully completed both tests your ESP FIREbeam is commissioned.  You can now fine tune 
your beam to suit the environment if needed.  Look through the following menus to see adjustments that can be 
made. 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for ESP FIREbeam

Page 1: ...esp FIREbeam INSTALLATION MANUAL www acornfiresecurity com www acornfiresecurity com...

Page 2: ...www acornfiresecurity com www acornfiresecurity com...

Page 3: ...2 Step 2 Programming the Analogue Address 6 2 3 Step 3 Mounting the Controller 7 2 4 Wiring Configuration 7 2 5 Step 4 Commissioning 8 2 5 1 Stage One Language and Commissioning Speed 8 2 5 2 Stage T...

Page 4: ...ESP FIREbeam comes boxed with the head unit low level controller one reflector 3mm allen key and quick start installation guide this should be used for distances over 5m and up to 40m 1 1 2 40 to 80 m...

Page 5: ...40m from the floor The maximum protected area either side of the beam can be extended by 1 for every degree of roof pitch see the example below NOTE Careful design consideration should be made when p...

Page 6: ...the front edge of the box Wire to low level controller using bottom colour coded terminals Screw in through holes provided outside of the rubber seal 2 2 Step 2 Programming the Analogue Address The F...

Page 7: ...this connection can be checked by reading the resistance across the black and grey terminals they will read 110 ohm if OK or 220 ohm if not connected properly 2 4 Wiring Configuration The output curre...

Page 8: ...in normal mode the system uses 3 5mA in fast mode it uses 17mA if you are commissioning more than one beam at a time and the system cannot support the extra draw it may be necessary to use normal mod...

Page 9: ...ng noticeably less read on below These figures are approximate but if you are receiving noticeably less than these figures you may be receiving a reflection from an object nearby and not the far wall...

Page 10: ...higher the AQ the quicker it will auto align This is done by manually moving the x and y motors to obtain a received signal from the reflector In the example below we can see that the reflector is bel...

Page 11: ...low 100 Now proceed to Step 4 Testing the final stage of commissioning 2 6 Step 5 Testing 2 6 1 Fault Test This is done to confirm that the returned signal is from the reflector Cover the entire refle...

Page 12: ...it will reset to normal automatically FAULT The beam path has been fully blocked within 1 second used when fault testing in commissioning ERROR No communication with the controller This could be that...

Page 13: ...ress down to go through the main menu options Select this option to change system language Select this option to commission the ESP FIREbeam Select this option to make all changes and adjustments to t...

Page 14: ...automatically stop when a received signal strength reaches 6 this received signal is the returned strength of the output signal without a reflector if no return signal is received the beam will reach...

Page 15: ...ved signal raises above the fire threshold hysteresis This can be set to latching if your system requires this Change by using the right and left keys Press enter to return to Mode Change or down to g...

Page 16: ...enter to return to Mode Change or down to go to Hysteresis Hysteresis Changing the hysteresis will change the delay in returning from a fire state back to a normal state For example the beam is facto...

Page 17: ...to Beam Maintenance or down to go to Alarm Fault Event Counts Alarm Fault Event Counts Here we can see how many times the beam has gone into fire or fault since the beam was commissioned or since the...

Page 18: ...t and left keys Press enter to return to Diagnostics or down to go to RX Sensitivity RX Sensitivity This screen shows the receiver sensitivity and can be changed by using the right and left keys Press...

Page 19: ...larm Condition adjustable 2 to 30 seconds in 1 second increments default 10 seconds Alarm Indication Controller Status FIRE Controller Red Flashing LED Head Red Flashing LED Alarm Relay Change Over CO...

Reviews: