IV. WIRING

Wiring for synchronized strobes and horn.

Using this method you may:

Use only two wires to synchronize the temporal horn and strobe with the ability to mute the horn (place 

switches 

1

and 

2

in the ON position on the HEC24, HEC3-24, HEC3-12, WHEC24).

Mute the horn 

only

when the temporal horn option has been selected.

Use the Hochiki America synchronization protocol to provide synchronize and mute the horn.    

Wiring for synchronized parallel (unison) horn/strobe operation.

Using this method you may:

Use four wires where two wires are used to power and synchronize the strobe and two additional wires are used 

to power and synchronize the horn (place switches 

1

and 

2

in the OFF position on the HEC24, HEC3-24, 

HEC3-12, WHEC24).

Choose either continuous horn and allow the FACP to control the horn or choose temporal horn and synchronize the horns with the Hochiki America synchronization protocol.  

Use the Hochiki America synchronization protocol to provide synchronization and mute the horn.    

NOTICE

FOR THIS OPTION, SWITCHES 1 AND 2 ON THE HEC24, HEC3-24, HEC3-12, WHEC24 MUST BE IN THE OFF POSITION TO ISOLATE POWER TO THE AUDIBLE AND VISIBLE 

PORTION OF THE CIRCUIT.

ALL STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS APPLIED VOLTAGE.  THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR PULSING 

SIGNALING CIRCUITS. HOWEVER, USE OF THE HAVSM CONTROL MODULE IS  PERMITTED TO SYNCHRONIZE THE STROBE AND/OR MUTE THE HORN.

REFERENCE HAVSM CONTROL MODULE MANUAL (550-0539, DATED 03/04/11) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS.  HAVSM MANUAL CAN BE OBTAINED AT 

HTTP://WWW.HOCHIKI.COM OR CALL HOCHIKI AMERICA CORPORATION AT 714-522-2246.

Conventional Method:

You may connect both the strobe and the horn directly from a source of rated power without the use of a control module.  However, the horns and strobe lights will NOT be synchronized.  Place

switches 

1

and 

2

in the ON position on the HEC24, HEC3-24, HEC3-12, WHEC24 to power both the audible and visible from a single pair of power wires. If you wish to power the horn and

strobe from independent sources of power, place switches 

1

and 

2

in the OFF position on the HEC24, HEC3-24, HEC3-12, WHEC24 and connect power to the appropriate terminals.

CAUTION:

When using only a single power source to

energize the strobe and horn (switches 1 and 2 in the

ON position), the in/out wiring must be under the S+ and

S- terminals only.  Failure to do so may result in damage

to your signal.  For the horn only (HEH24 and HEH12)

and strobe only (HES24, HES3-24, HES3-12, WHES24),

only the top three terminals are to be used.  

SWITCH POSITION

TONE

3

4

5

Mechanical Temporal 3

ON

ON

ON

Mechanical - Continuous

OFF

ON

ON

2400Hz - Temporal 3

ON

OFF

ON

2400Hz - Continuous

OFF

OFF

ON

Chime - Temporal 3

ON

ON

OFF

Chime - Continuous

OFF

ON

OFF

Whoop

ON

OFF

OFF

Whoop

OFF

OFF

OFF

CAUTION:

A jumper card is provided to test for correct wiring

in the supervisory mode only.  DO NOT pass alarm 

current through the jumper.

Mounting Bracket:

Allows the installer to pre-wire the system, test

for system supervision, remove the signal head

until occupancy, switch out Hochiki America 

signals without changing mounting brackets and

has locking edge connector for snap-in-place

installation.

Instant Voltage Verification:  

It is often necessary to confirm the voltage drop

along a line of devices. The access holes are

provided in the back of the terminal block to

allow the voltage to be measured directly 

without removing the device. Typically this

would be done at the end of the line to confirm

design criteria. Most measurements will be

taken using the S+ and S- locations although

access is provided to other locations. 

NOTICE:

CARE SHOULD BE TAKEN TO NOT

SHORT THE TEST PROBES.

NOTICE: 

SWITCH POSITIONS 1 AND 2 IN THE OFF POSITION TO 

SELECT ISOLATED HORN AND STROBE POWER INPUTS

SWITCH POSITION 6 ON = HIGH DBA

SWITCH POSITION 6 OFF = LOW DBA

Summary of Contents for HEC24 Series

Page 1: ... horn only appliances shall have their tops above the finished floors at heights of not less than 90 in 2 30m and below the finished ceilings at heights of not less than 6 in 152mm Different mounting heights shall be permitted by the AHJ provided the sound pressure level requirements of NFPA 72 are met III MOUNTING ROUGH IN BOX AND RUN WIRING This unit is designed for mounting to most single gang ...

Page 2: ...nuous Chime 70 dBA 66 dBA 15 30 Whoop 82 dBA 69 dBA 56 62 HORN DECIBEL AND CURRENT RATINGS PRODUCT INFORMATION Horn Decibel Levels Horn Current Ratings Over Input Voltage Range of 8 17 5V Horn Mode Minimum SPL at 10Ft Per ANSI UL 464 HIGH Minimum SPL at 10Ft Per ANSI UL 464 LOW Regulated 12VDC Max Operating Current mA HIGH Setting Regulated 12VFWR Max Operating Current mA HIGH Setting Temp 3 2400H...

Page 3: ...e lights will NOT be synchronized Place switches 1 and 2 in the ON position on the HEC24 HEC3 24 HEC3 12 WHEC24 to power both the audible and visible from a single pair of power wires If you wish to power the horn and strobe from independent sources of power place switches 1 and 2 in the OFF position on the HEC24 HEC3 24 HEC3 12 WHEC24 and connect power to the appropriate terminals CAUTION When us...

Page 4: ...h laws regulations and rules to particular fact patterns Each person s activities can differently affect the obligations that exist under applicable laws regulations or rules Therefore these materials should be used only for informational purposes and should not be used as a substitute for seeking professional legal advice Hochiki America will not be responsible for any action or failure to act in...

Reviews: