background image

HUSH-ACTIV KITS

 

BS

 

5839-6 Grade C Domestic Fire Alarm Kits

INSTALLER’S GUIDE

 

Approved Document No. DFU0005086 Rev 3

The Hush-ActiV standalone domestic fire alarm kits have been designed to reduce the 
incidence of false alarms in HMOs, dwellings, flats, etc., by providing a reliable, fully 
monitored fire detection and alarm system complete with hush (silence) and test functions.

3

CONTROLLER

230V AC

ActiV

Multisensor

CONVENTIONAL ZONE & SOUNDER CIRCUITS

HUSH-ACTIV CONTROLLER

ActiV

Smoke Detector

ActiV

Heat Detector

ActiV

Base Sounder

S

HPPSU

230V/24V

HA508

3

3

EOL Resistor

(Sounders)

EOL Capacitor

(Detectors)

2

1 of 3

Approved Document No. DFU0005086 Rev 3

HUSH-ACTIV WIRING AND CONNECTIONS 

(see Fig.2 for typical connections)

All wiring must be installed in accordance with all applicable national, regional or local 
standards. In the UK this is BS

 

7671 (Wiring Regulations) and BS

 

5839-6 (Grade C System).

External

230V/24V

PSU

(HPPSU)

+Ve

0v

CONN1

Li-Ion 

Battery

-

ZONE

+

PLK4

DC

24V

-

SNDR

+

ZONE 

+

ZONE 

-

SNDR 

+

CONV ZONE 

CIRCUIT

ActiV Multisensor

+ Diode Base

ActiV Heat Detector

+ Diode Base

EOL Capacitor

+Ve

ActiV

Base Sounder

-Ve

EOL Resistor

S

+Ve

CONV SOUNDER

CIRCUIT

-Ve

-Ve

+Ve

S

+Ve

ActiV Smoke Detector

+ Diode Base

-Ve

Connect EOLs
in last device
on both sounder
and zone circuits.

Optional 470 ohm

Call Point

(Not supplied)

Additional ActiV

Base Sounder
(Not supplied)

1

2

3

4

ON

SW2

PL2

CON1 (-ZONE+): The conventional zone circuit connects up 
to 16 ActiV detectors (3 detectors supplied with each kit). 
Use the supplied diode bases (C4408D) with the detectors.
CON1 (-SNDR+): The conventional sounder circuit connects 
up to 8 ActiV sounders (1 sounder supplied with each kit).

CON1 (DC 24V): Connects to 24V external PSU. Typically, 
1mm to 1.5mm twin & earth cable may be used.

PLK4: Battery connector. To reduce battery drain, it is 
recommended that the battery is connected after the 
external 24V power is applied.

Fig.1 - Typical HAK/1 Hush-ActiV System

FIRE ALARM

ancillaries

FIRE ALARM

ancillaries

THIS EQUIPMENT MUST BE INSTALLED AND MAINTAINED BY A SUITABLY SKILLED AND 
TECHNICALLY COMPETENT PERSON. ENSURE ALL POWER IS REMOVED BEFORE INSTALLATION.

Max. number of ActiV 
conventional devices per system:

16 ActiV detectors (multisensor, heat, smoke) plus 8 ActiV sounders. 
Note: See list above for devices supplied with Hush-ActiV kits.

Max. length of device circuit:

200m

Maximum load:

100mA

Operating voltage:

24Vdc

Quiescent current:

5mA

Replaceable battery (2Ah):

Li-Ion rechargeable battery (C-TEC supplied only, up to 10 year life).
For 16 devices, provides >72 hour standby plus 5 minute alarm 

(under normal use).

PL2 open collector outputs:

Each output max 20mA @ 30V.

LED indicators:

Supply (Green) LED. Lit steady when powered from the external PSU. Lit flashing 
when external PSU fails and the unit is only powered from the onboard battery.
Fault (Yellow) LED. Lit flashing when there is a wiring / battery fault, device head out.
Alarm (Red) LED. Lit steady when there is a fire alarm.
Hushed (Amber) LED. Lit steady when the unit is in a hushed (silenced) state.

Onboard beeper: Provides audible feedback when a button is pressed and in a fire / fault condition.
Control buttons: 1 x TEST button & 1 x HUSH button - see ‘Hush-ActiV Operation’ overleaf.
Dimensions (mm): 144 (W) x 84 (H) x 25 (D)

Body Material:

PVC

Weight:

160g

IP Rating (EN 60529): IP40 (indoor use only)

Operating Temp.: -10

0

C to +55

0

C

Humidity:

Max. 95% RH (non-condensing)

HUSH-ACTIV TECHNICAL SPECIFICATION

Fig.2 - Typical HAK/1 Hush-ActiV Connections

Fit 35mm deep double gang UK back boxes for both the Hush-ActiV Controller (HA508) and 
the Hush PSU (HPPSU). The Hush-ActiV system should be tested monthly per BS

 

5839-2, or 

applicable national, regional or local regulations.

2 of 3

Advantages of a BS

 

5839 Part 6 Grade C system over a Grade D system

•  Fault monitoring of the power supply.

•  Fault monitoring of the interconnecting wiring.

•  Allows residents to silence & test the system at floor level.

•  Does not require mandatory replacement of devices every ten years.

Read these instructions before installation and operation

Refer to the individual 

instructions supplied with 

each ActiV device for 

wiring and specifications.

Note: Connect the supplied EOL capacitor and EOL resistor across the terminals of the last 
device on each circuit to allow the wiring to be line monitored for open and short circuit faults.

All -Ve terminals on CON1 are common -Ve. Typically, the conv. detector (ZONE) and sounder 
(SNDR) circuits may be wired using 3-core cable, e.g. 1mm to 1.5mm triple & earth cable. All 
terminals can accept cables up to 1.5mm. Alternatively, separate 2 x 2-core cable may be used.

HAK/1 

KIT CONTENTS

1 x Hush-ActiV BS

 

5839-6 Grade C Controller (Part No. HA508)

1 x 230V/24V PSU (Part No. HPPSU)

1 x ActiV Multisensor Fire Detector (Part No. C4414)

1 x ActiV Optical Smoke Detector (Part No. C4416)
1 x ActiV Heat Detector (Part No. C4403A2)
3 x ActiV Detector Diode Bases (Part No. C4408D)
1 x ActiV Base Sounder (Part No. BF431C/CC/W) c/w white lid (Part 

No. BF330CTLIDW) & adaptor plate (Part No. BF431QCP)
1 x 0.47

μ

F 50V EOL capacitor; 1 x 6K8 0.25W EOL resistor

HAK/2 

KIT CONTENTS As HAK/1, except 2 x Smoke Detectors, 0 x Multisensor Detector

HAK/3 

KIT CONTENTS As HAK/1, except 2 x Multisensor Detectors, 0 x Smoke Detector

DIP Switch SW2 1-4 Settings:
DIP1 ON = Delay fire open collector 
for 2 minutes - Default OFF.
DIP2 ON = Test mode triggers fire 
open collector output - Default OFF.
DIP3 & DIP4 = For future expansion.

1

2

3

4

ON

(ON)

(OFF)

SW2

PL2 Notes:
1. The wiring to this connection is NOT monitored.
2. The outputs will NOT function with a mains 
  fail at the HPPSU and therefore must NOT to  
  be used for life safety purposes.
3. The sounder trigger input is NOT monitored  
  and will sound at the same tone as the  
  domestic fire level 1 (FL1) of the Hush-ActiV 
  system, i.e. there is no separate domestic fire  
  level 2 (FL2) indications or sound.

Refer to Application Note 0014.1 for PL2 
connection details (available 

@

 

www.c-tec.com

).

PL2: Remote Connection.