background image

HOBO MX2300 Series Data Logger Manual 

1-800-LOGGERS 

www.onsetcomp.com 

 

5.

 

Enable the Low Alarm if you want an alarm to trip when the 

sensor reading falls below the low alarm value. Drag the 

slider to the reading that will trip the alarm or tap the value 

field and type a specific reading. In the example, an alarm is 

configured to trip when the temperature falls below 32°F. 

Note:

 The actual values for the high and low alarm limits are 

set to the closest value supported by the logger. 

6.

 

Under Raise Alarm After, select the duration before an 

alarm is tripped and tap Done in the Alarm Duration screen. 

7.

 

Select either Cumulative or Consecutive Samples. If you 

select Cumulative Samples, then the alarm will trip when 

the time the sensor is out of range over the course of the 

deployment is equal to the selected duration. If you select 

Consecutive Samples, then the alarm will trip when the 

time the sensor is continuously out of range is equal to the 

selected duration. For example, the high alarm for 

temperature is set to 85°F and the duration is set to 30 

minutes. If Cumulative is selected, then an alarm will trip 

once a sensor reading has been at or above 85°F for a total 

of 30 minutes since the logger was configured; specifically, 

this could be 15 minutes above 85°F in the morning and 

then 15 minutes above 85°F again in the afternoon. If 

Consecutive is selected, then an alarm will trip only if all 

sensor readings are 85°F or above for a continuous 30-

minute period. 

8.

 

Tap Done and repeat steps 3–8 for the other sensor if 

desired. 

9.

 

Back in the Configure screen, a setting to maintain the 

alarm until the logger is reconfigured is enabled 

automatically. This cannot be disabled. 

10.

 

Tap Start in the Configure screen to load the alarm settings 

onto the logger if you are ready to start. 

When an alarm trips, the logger alarm LED blinks every 4 

seconds (unless Show LED is disabled), an alarm icon appears in 

the app, and an Alarm Out of Range event is logged. Even if the 

reading returns to a normal range, the alarm indicator will not 

clear in the app and the alarm LED will continue to blink. 

Notes: 

 

Alarms are checked <placeholder>.

 

 

The actual values for the high and low alarm limits are set 

to the closest value supported by the logger. For 

example, the closest value to 85°F that the logger can 

record is 84.990°F and the closest value to 32°F is 

32.043°F. In addition, alarms can trip or clear when the 

sensor reading is within the logger specifications of 

0.04°C resolution. This means the value that triggers the 

alarm may differ slightly than the value entered. For 

example, if the High Alarm is set to 75.999°F, the alarm 

can trip when the sensor reading is 75.994°F (which is 

within the 0.04°C resolution). 

 

When you read out the logger, alarm events can be 

displayed on the plot or in the data file. See 

Logger 

Events

 

If the logger was configured to stop logging with a button 

push, any tripped alarms will be cleared automatically 

when logging is stopped and no Alarm Cleared event will 

be logged in the data file. This ensures that the logger will 

start checking for alarm conditions when logging resumes 

(if the logger was configured with Allow Button Restart 

selected).

 

Burst Logging 

Burst logging is a logging mode that allows you to set up more 

frequent logging when a specified condition is met. For 

example, a logger is recording data at a 5-minute logging 

interval and burst logging is configured to log every 30 seconds 

when the temperature rises above 85°F (the high limit) or falls 

below 32°F (the low limit). This means the logger will record 

data every 5 minutes as long as the temperature remains 

between 85°F and 32°F. Once the temperature rises above 

85°F, the logger will switch to the faster logging rate and record 

data every 30 seconds until the temperature falls back to 85°F. 

At that time, logging then resumes every 5 minutes at the 

normal logging interval. Similarly, if the temperature falls below 

32°F, then the logger would switch to burst logging mode again 

and record data every 30 seconds. Once the temperature rises 

back to 32°F, the logger will then return to normal mode, 

logging every 5 minutes. 

Note:

 Sensor alarms, statistics, and the 

Stop Logging option “Wrap When Full” are not available in 

burst logging mode. 
To set up burst logging: 
1.

 

Tap the HOBOs icon and tap the logger to connect to it. If 

the logger was configured with Power Saving Mode 

enabled, press the button on the logger to wake it up. 

When working with multiple loggers, you can also press the 

button on the logger to bring it to the top of the list. 

2.

 

Once connected, tap Configure. 

3.

 

Tap Logging Mode and then tap Burst Logging. 

4.

 

Tap a sensor under Burst Sensor Limits. 

5.

 

Enable High Limit if you want burst logging to occur when 

the sensor reading rises above a specific reading. Drag the 

slider to the reading that will trigger burst logging or tap the 

value field and type a specific reading. In this example, the 

logger will switch to burst logging when the temperature 

rises above 85°F. 

Summary of Contents for MX2303

Page 1: ...ernal temperature sensor xx minutes in air moving 1 m sec MX2303 and MX2304 external sensors xx minutes in air moving 1 m sec xx seconds in stirred water Stability Drift 0 01 C 0 018 F per year Relati...

Page 2: ...ll be illuminated for 4 seconds Status LED This LED blinks blue every 4 seconds when the logger is logging unless Show LED is disabled as described in Configuring the Logger If the logger is waiting t...

Page 3: ...n on the logger for 10 seconds to reset a password Update Firmware When new logger firmware is available this action appears in the list Select it and follow the instructions on the screen Note that i...

Page 4: ...then tap Done For example select 30 days if you want the logger to log data for 30 days after logging begins d Tap Done in the Stop Logging screen 9 Select the sensor measurement types that will be lo...

Page 5: ...r clear when the sensor reading is within the logger specifications of 0 04 C resolution This means the value that triggers the alarm may differ slightly than the value entered For example if the High...

Page 6: ...r is stopped with a button push while in burst logging mode then a New Interval event is automatically logged and the burst condition is cleared even if the actual high or low condition has not cleare...

Page 7: ...ect to it If the logger was configured with Power Saving Mode enabled press the button on the logger to wake it up When working with multiple loggers you can also press the button on the logger to bri...

Page 8: ...y life is 1 year typical with a logging interval of 1 minute but may be extended to 2 years when the logger is configured with Power Saving Mode enabled Expected battery life varies based on the ambie...

Page 9: ...nect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help This device complies with Part 1...

Reviews: