OM-235 281 Page 20
3-14. Serial Number And Rating Label Location
The serial number and rating information for this product is located on back. Use rating label to determine input power requirements and/or rated output.
For future reference, write serial number in space provided on back cover of this manual.
3-15. Selecting A Location And Connecting Input Power
Ref. 242 691-A / 802 286-E
!
Do not move or operate unit
where it could tip.
18 in. (457 mm) of
space for airflow
!
Installation must meet all National
and Local Codes
−
have only quali-
fied persons make this installation.
!
Special installation may be
required where gasoline or volatile
liquids are present
−
see NEC Ar-
ticle 511 or CEC Section 20.
!
Disconnect and lockout/tagout in-
put power before connecting input
conductors from unit.
!
Always connect green or green/yel-
low conductor to supply grounding
terminal first, and never to a line
terminal.
4
Plug (NEMA Type 6-50P)
5
Receptacle NEMA Type 6-50R)
Connect plug to receptacle.
6
Input Power Cord.
7
Black And White Input Conductor (L1
And L2)
8
Green Or Green/Yellow Grounding
Conductor
9
Disconnect Device (switch shown in
the OFF position)
10 Disconnect Device Grounding
Terminal
11 Disconnect Device Line Terminals
Connect green or green/yellow grounding
conductor to disconnect device grounding
terminal first.
Connect input conductors L1 and L2 to dis-
connect device line terminals.
12 Over-Current Protection
Select type and size of over-current
protection using Section 3-13 (fused dis-
connect switch shown).
Close and secure door on disconnect
device. Remove lockout/tagout device,
and place switch in the On position.
L1
L2
230 VAC, 1
2
1
3
4
5
6
7
8
9
L1
L2
1
=GND/PE Earth Ground