HV580L Series Frequency Inverter
167
Setting range
0
~
3
PC-50
Time unit of simple PLC running Default
0
Setting range
0
S (Second)
1
H (Hours)
PC-51
Reference 0 source
Default
0
Setting range
0
Set by PC-OO
1
VS
2
AS
3
VS2
4
PULSE Pulse
5
PID
6
Set by preset frequency (P0-08),
modified via terminal UP/DOWN
It determines the setting channel of reference 0. You can perform convenient switchover between the setting
channels. When multi-reference or simple PLC is used as frequency source, the switchover between two
frequency sources can be realized easily.
Group PD: Communication parameters
Please refer to the "HV580L communication protocol".
Group PP: User’s password
PP-00
User’s password
Default
0
Setting range
0
~
65535
If it is set to any non-zero number, the password protection function is enabled. After a password has been set
and taken effect, you must enter the correct password in order to enter the menu. If the entered password is
incorrect you cannot view or modify parameters.
If PP-00 is set to 00000, the previously set user password is cleared, and the password protection function is
disabled.
PP-01
Restore default
settings
Default
0
Setting range
0
No option
settings
1
Restore factory settings except motor
parameters
2
Clear records
4
Restore user backup parameters
501
Back up current user parameters