3.6 ASCII messages
Communication from the ASCII side is carried out thanks to simple ASCII messages. Note that these messages can be
configured from the configuration tool to match the ASCII master device.
The ASCII messages used to read/write points into the gateway through this interface have the following format
•
Message to read a point's value:
ASCII_String
?
\r
Where:
Characters
Description
ASCII_String
String indicating the point's address inside the gateway
?
Character use to indicate that this is a reading message
(configurable from the configuration tool)
\r
Carriage return
character
(HEX 0x0D, DEC 13)
•
Message to write a point's value:
ASCII_String
=
vv
\r
Where:
Characters
Description
ASCII_String
String indicating the point's address inside the gateway
=
Character use to indicate that this is a reading message
(configurable from the configuration tool)
vv
Current point’s value
\r
Carriage return
character
(HEX 0x0D, DEC 13)
•
Message informing about a point's value (sent spontaneously by the gateway when receiving a change
from BACnet or sent by the gateway in response to a previous poll for the point):
ASCII_String
=
vv
\r
Where:
Characters
Description
ASCII_String
String indicating the point's address inside the gateway
=
Character use to indicate where point’s data starts
vv
Current point’s value
\r
Carriage return
character
(HEX 0x0D, DEC 13)