Safety, Environmental & Regulatory Information
5 (24)
3
Safety, Environmental & Regulatory Information
3.1
Scope
This chapter addresses safety, environmental & regulatory information for the Ewon Cosy+.
3.2
Power Supply
The external power supply is a third party device that is not part of this certification.
The equipment should be supplied from external, separately provided power supply 12-24Vdc,
30W min., certified for 60°C and for altitudes up to 2000m. Power supply should be separately
certified according to UL/IEC 62368-1 with ES1, PS2 output (for more information, refer to
Specification of the External Power Supply, p. 20
3.3
Applicable Directives, Standards and Compliance
The product described in the present Installation Guide complies with the CE and the FCC
regulations.
For all documents related to certifications such as CE Declaration of conformity, FCC declaration
of conformity, UL/CB certificate and EC Type Examination certificate, please refer to the
.
3.4
Field Implementation & Environmental Conditions
3.4.1
General Restriction
This equipment is not suitable for use in locations where children are likely to be present.
3.4.2
Ingress Protection
The Ewon Cosy+ has an IP20 protection grade.
Therefore, the Ewon Cosy+ is
NOT
suited for outdoor mounting. It has to be integrated in an
electrical cabinet, protected from excessive heat, humidity and dust.
Do not push any sharp object into the air vents or openings of the equipment.
3.4.3
Mounting Recommendations
The product is intended to be mounted vertically, label on the right side.
The normal mounting position of the Ewon Cosy+ is to be mounted on a horizontal
Omega type DIN-rail (EN 50022)
.
•
Mounting the unit on DIN-rail
Pull the slide lock (located at the bottom of the back-side of the unit) downwards and
present the unit in front of the DIN rail. Tilt the Cosy+ upwards in order to hang it on the
upper edge of the DIN rail by its hook. Gently tilt the unit downwards until it finds its
original position. Pull the slide lock upwards to fix and lock the unit on the DIN rail.
•
Removing the unit from DIN-rail
Release the unit by pulling the slide lock downwards while gently tilting the unit upwards.
Free the unit by unhooking it from the upper rail edge.
Ewon Cosy+ Installation Guide
IG-0031-00 1.0 en-US