45 (60)
Index
Object Name
Subindex
Description
Type
Access
Notes
1011h
Restore Parameters 00h
Largest subindex supported
U8
RO
01h
01h
Restore all parameters
U32
RW
To restore the default values
of a configuration, write
“load” = 6C 6F 61 64h to this
object.
3
1014h
COB-ID EMCY
00h
Defines the COB-ID of the
Emergency Object
U32
RO
1016h
Consumer
Heartbeat Time
00h
Largest subindex supported
U8
RO
7Fh
01h - 80h
The consumer heartbeat time
defines the expected heartbeat
cycle time and has to be higher
than the corresponding
producer heartbeat time.
Monitoring starts after the
reception of the first heartbeat.
Not used if 0
U32
RW
Heartbeat Time.
Bits 31–24: reserved
Bits 23–16: NodeID
Bits 15–0: Heartbeat Time
Value must be a multiple of 1
ms.
Up to 127 nodes can be
monitored.
1017h
Producer Heartbeat
Time
00h
Defines the cycle time of the
heartbeat. Not used if 0
U16
RW
The time must be at least 10
ms and a multiple of 1 ms
1018h
Identity object
00h
Number of entries
U8
RO
04h
01h
Vendor ID
U32
RO
1Bh (HMS Industrial
Networks)
02h
Product Code
U32
RO
18h (Anybus X-gateway
CANopen)
03h
Revision Number
U32
RO
Current software revision
04h
Serial Number
U32
RO
HMS serial number
1029h
Error behavior
object
00h
Number of entries
U8
RO
01h
Communication error
U8
RO
00h: Change to
Preoperational if currently in
NMT state Operational
02h
Profile or manufacturer specific
error
U8
RO
00h: Change to
Preoperational if currently in
NMT state Operational
1400h
...
147Fh
Receive PDO
parameter
00h
Largest subindex supported
U8
RO
02h
01h
COB-ID used by PDO
U32
RW
-
02h
Transmission type
U8
RW
See
1600h
...
167Fh
Receive PDO
mapping
00h
No. of mapped application
objects in PDO
U8
RW
-
01h
Mapped object #1
U32
RW
-
02h
Mapped object #2
U32
RW
-
03h
Mapped object #3
U32
RW
-
04h
Mapped object #4
U32
RW
-
05h
Mapped object #5
U32
RW
-
06h
Mapped object #6
U32
RW
-
07h
Mapped object #7
U32
RW
-
08h
Mapped object #8
U32
RW
-
1800h
...
187Fh
Transmit PDO
parameter
00h
Largest subindex supported
U8
RO
05h
01h
COB-ID used by PDO
U32
RW
-
02h
Transmission type
U8
RW
See
03h
Inhibit time
U16
RW
In steps of 0.1 ms
05h
Event Timer (ms)
U16
RW
-
Anybus
®
X-gateway
™
CANopen
®
PROFINET
®
IRT (2.32) User Manual
SCM-1202-029 1.2 en-US
3.
The byte order may have to be changed depending on the method of writing to this object.