![HMS Anybus X-gateway CANopen User Manual Download Page 14](http://html1.mh-extra.com/html/hms/anybus-x-gateway-canopen/anybus-x-gateway-canopen_user-manual_2141720014.webp)
12 (60)
3.7
LED Indicators
1 2
3
5
4
6
LED 1 to 4
Primary network interface status
LED 5
Secondary CANopen network interface status
LED 6
Device operation status
LED Indicators – Primary PROFINET IRT Network Interface
1 - Network Status
Off
Offline
– No power
– No connection to IO Controller
Green
Online (RUN)
– Connection to IO Controller
Green, 1 flash
Online (STOP)
– Connection to IO Controller
– IO Controller in STOP state or IO data bad
– RT synchronization not finished
Red
Fatal error
Red, 1 flash
Station name error
Red, 2 flashes
IP address error
Red, 3 flashes
Configuration error
Alternating red/green
Firmware update in progress
2 - Module Status
Off
No power or initializing
Green
Normal operation
Green, 1 flash
Diagnostic event present
Red
Fatal error
Alternating red/green
Firmware update in progress
3 - Link/Activity 1
4 - Link/Activity 2
Off
No power or no link detected
Green
Link OK
Green, flickering
Transmitting/receiving data
LED Indicators – Secondary CANopen Network Interface & Device Status
5 - CANopen Status
Off
No power
Flickering red/green
LSS services in progress
Green
Operational state
Green, 1 flash
Stopped state
Green, blinking
Pre-operational state
Red
Bus off
Red, 1 flash
Warning limit reached
Red, 2 flashes
Error control event
Red, 3 flashes
Sync error
Red, 4 flashes
Data communication timeout
Red, blinking
Configuration error
6 - Device Status
Off
Power off
Green
Running
Green, 1 flash
Bootup
Red
Fatal error
Red, 1 flash
Initialization error
Red, 2 flashes
Timeout error
Red, 3 flashes
Hardware failure
Red, 4 flashes
Invalid switch settings
Anybus
®
X-gateway
™
CANopen
®
PROFINET
®
IRT (2.32) User Manual
SCM-1202-029 1.2 en-US