HMS Networks Intesis INMBSMHI048O000 User Manual Download Page 12

Intesis

TM

 Modbus Server 

– Mitsubishi Heavy Industries AC 

 

User’s Manual r1.0 eng

 

    

 

  

 

 

 

 

 

© HMS Industrial Networks S.L.U - All rights reserved 

This information is subject to change without notice

 

 

  URL    https://www.intesis.com  

 
 

                12 / 26

 

 

Connect to Mitsubishi Heavy Industries Interface

 

Use  the  A-B  connector  in  the  right  top  corner  of  the  front  side  of  the  Intesis

TM

  device  in 

order  to  connect  the  Mitsubishi  Heavy  Industries  network  (Superlink)  to  the  Intesis

TM

Recommended specifications of the cable for the Superlink are shown as follows: 
 

 

Size of cable : 0.75 to 1.25 square mm 

 

Max length of wiring : total 1000m (loop wiring is not allowed) 

 

Cable materials : 

 

Twisted Vinyl Cabtyre Cable 

VCTF  2 core  0.75 to 1.25 square mm  

Twisted Vinyl Cabtyre Cable 

VCT  2 core  0.75 to 1.25 square mm 

Twisted Vinyl Cable for Control 

CVV  2 core  0.75 to 1.25 square mm 

 

Table 3.1 

Cable types recommended for Superlink connection 

 

 

For prevention of electromagnetic noise malfunctions, parallel wiring with the power 
line should be avoided 

 
Select  the  appropriate  Superlink  mode  in  the  SLK  selector.  If  you  are  using  latest  Air 
Conditioner of the Mitsubishi Heavy Industries  network (New Superlink) select NEW, if not 
select OLD.  
 
LEDs placed in the top left corner will show connection status as follows: 

 

LED 

Status 

Intesis

TM

 behavior 

OP 

Blinking 

Power supply OK

 

ERR 

Off 

No error 

HOST 

Blinking 

Internal communication OK 

PAC 

Blinking 

Communication with the Superlink network OK 

 

Table 3.2 

Intesis

TM

 LED status information 

 
 
OP LED behavior must defer depending on the Superlink version, as shown in 

Figure 3.3

 

 

 
 
 
 
 
 
 

Figure 3.3 

OP LED blinking behavior depending on

 

Superlink version 

 
 
If LEDs (except ERR) are not in the states described above, check section 5.3. 

 

For  further  information  about  the  Superlink  network,  look  up  the  Mitsubishi  Heavy 
Industries Manual or contact your nearest Mitsubishi Heavy Industries supplier. 

 

Connect to Modbus Interface 

3.2.1

 

Connect to Modbus RTU 

Connect the communication cable coming from the Modbus RTU network to Intesis

TM 

device 

(see 

Figure 3.1

). There are 2 existing modes available: 

 

Superlink-II 

 
 

Superlink-I 

On 

 

Off 

On 

 

Off 

1 sec 

Summary of Contents for Intesis INMBSMHI048O000

Page 1: ...Mitsubishi Heavy Industries Air Conditioning Gateway for integration of Mitsubishi Heavy Industries air conditioning systems into Modbus RTU and TCP systems USER MANUAL Issue date 05 2012 r1 0 ENGLISH...

Page 2: ...tive purposes and are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the...

Page 3: ...U All rights reserved This information is subject to change without notice URL https www intesis com 3 26 Gateway for integration of Mitsubishi Heavy Industries air conditioning systems into Modbus RT...

Page 4: ...ndoor units 10 IntesisTM Device Connections 11 Connect to Mitsubishi Heavy Industries Interface 12 Connect to Modbus Interface 12 3 2 1 Connect to Modbus RTU 12 3 2 2 Connect to Modbus TCP 13 3 2 3 Co...

Page 5: ...Modbus master read and write in the Modbus registers Moreover IntesisTM includes all hardware required to manage control Mitsubishi Heavy Industries indoor units without extra components needed Integ...

Page 6: ...response of a certain device is detected the corresponding virtual signal inside the gateway will be activated indicating communication error between the gateway and that precise device see 0 When a...

Page 7: ...revious Superlink or Superlink II New Superlink Indoor Unit actual address range is 00 to 47 INMBSMHI128O000 Model supporting up to 128 indoor units For Superlink II New Superlink Indoor Unit actual a...

Page 8: ...ts are always expressed in MSB LSB Bid Endian Modbus error codes are fully supported they will be sent whenever a non valid Modbus action or address is required see section 9 Modbus RTU Baud rate can...

Page 9: ...W SetPoint Temperature Celsius value 16 C to 30 C 5 R W Fan Speed 0 Low 1 Medium 2 High 3 Powerful 6 R W Remote Controller Lock Unlock 0 Remote Controller Locked 1 Remote Controller Unlocked 7 R W Lou...

Page 10: ...Communication Status 2542 R W Indoor Unit On Off 2543 R W Operation Mode 2544 R W SetPoint Temperature 2545 R W Fan Speed 2546 R W Remote Controller Lock Unlock 2547 R W Louver Control 2548 R Room Te...

Page 11: ...ce connector s description 1 Modbus RTU master EIA485 C1 8 Reset button Non supported 2 Modbus RTU master EIA232 C2 9 Superlink selector SLK New Superlink II Old Superlink I 3 Console serial port EIA2...

Page 12: ...ring with the power line should be avoided Select the appropriate Superlink mode in the SLK selector If you are using latest Air Conditioner of the Mitsubishi Heavy Industries network New Superlink se...

Page 13: ...A232 cable pin assign Cable 2 wire EIA485 TX RX TX RX TX RX TX RX Table 3 4 EIA485 cable pin assign To check connectivity and correct functioning use LinkBoxMB software see LinkBoxMB User Manual 3 2 2...

Page 14: ...o PC LinkBoxMB Connect the IntesisTM device to the PC serial port using the serial cable provided One end should be connected to the Console EIA232 port of the IntesisTM device see Figure 3 1 and the...

Page 15: ...ishi Heavy Industries indoor unit s integration to Modbus networks will be covered Connections configuration To configure the IntesisTM s connection parameters and to see the points list press on the...

Page 16: ...eave it blank if no router is needed 5 Port Enter the TCP port to use default for Modbus TCP is 502 6 Timeout Keep Alive Enter the time expressed in seconds that IntesisTM will wait upon no TCP activi...

Page 17: ...tting up 128AC for INMBSMHI128O000 48AC for INMBSMHI048O000 3 Timeout response Maximum amount of time permitted before activating the Communication Error signal It is expressed in milliseconds ms and...

Page 18: ...ues Possible values for the signal See section 2 5 for further detail on address mapping and the possible values on each signal Sending the configuration to IntesisTM When the configuration is finishe...

Page 19: ...s window shows all signals active within the gateway with its main configuration parameters and its real time value1 in the Value column Figure 4 6 LinkBoxMB Signals Viewer The signals viewer can be u...

Page 20: ...the values configured through the Connection tab in IntesisTM configuration MHI LBOX Binary file created from the information in the files described above This is the file downloaded to the IntesisTM...

Page 21: ...etup program supplied for this and follow the instructions given by the Installation wizard 2 Install IntesisTM in the desired installation site For your convenience check external enclosure measures...

Page 22: ...aly Superlink communication failure Check Superlink cables and terminals connectors length of cables etc HOST Off Configuration error Download the binary file again see 4 3 PAC Off Communication error...

Page 23: ...rted TCP RTU EIA232 or EIA485 Modbus TCP configuration parameters IP address Subnet mask Default gateway address TCP port Modbus RTU configuration parameters EIA232 EIA485 Baud rate Parity Slave numbe...

Page 24: ...ject to change without notice URL https www intesis com 24 26 Mechanical Electrical characteristics 1 Device can be installed in any position 5 mm 195 mm 138 mm 10 mm 15 mm Figure 7 1 External dimensi...

Page 25: ...ivity LNK ACT 4 x MHI Interface OP ERR HOST PAC Push buttons 1 x Reset Device Selectors 1 x SLK selector Console port EIA232 DB9 female DCE SELV Configuration Via console port 2 Firmware Allows upgrad...

Page 26: ...ase on power supply at primary side 33 E33 Inverter primary current error 35 E35 Cooling overload operation 36 E36 Discharge pipe temperature error 37 E37 Outdoor heat exchanger temperature thermistor...

Reviews: