HMS Networks Intesis INMBSMHI048O000 User Manual Download Page 22

Intesis

TM

 Modbus Server 

– Mitsubishi Heavy Industries AC 

 

User’s Manual r1.0 eng

 

    

 

  

 

 

 

 

 

© HMS Industrial Networks S.L.U - All rights reserved 

This information is subject to change without notice

 

 

  URL    https://www.intesis.com  

 
 

                22 / 26

 

 

Troubleshooting 

If  Intesis

TM

  is  not  working  properly  or  even  not  working  at  all,  please  check  the  following 

conditions to be accomplished. 

5.3.1

 

Physical checking 

First point to look at to make sure that Intesis

TM

 is not working properly is to check physical 

connections: 
 
 

1.- Make sure that the power plug is correctly connected and current is available in 

 

the power line. 

 
 

2.- Check Intesis

TM

 LED status: 

 

LED 

Status 

Explanation 

Solution 

OP 

Off 

No  power  reaching  the 
internal device 

Check power connection 
Check fuse status 

(see 13 in Figure 3.2) 

ERR 

Blinking once 

perdiodicaly 

Superlink 
communication failure 

Check Superlink cables and terminals 
(connectors, length of cables, etc.) 

HOST 

Off 

Configuration error 

Download the binary file again 

(see 4.3)

 

PAC 

Off 

Communication error in 
the Superlink network 

Check the Mitsubishi Heavy Industries 
Superlink network and its connections 

 

Table 5.1

 Intesis

TM

 LED status information 

 

5.3.2

 

Software checking 

Once  physical  connections  have  been  checked,  if  functioning  problems  still  remain,  please 
use the LinkBoxMB tool to monitor the working status of the device. 
 

 

To check the Modbus  communication status, click on the 

Modbus

 button in the 

menu bar

 (see Figure 4.1). 

 

To  check  the  MHI  communication  status,  click  on  the 

MHI

  button,  also  in  the 

menu bar

 (see Figure 4.1). 

 

To check the signal values in the Modbus registers, click on the 

Signals

 button, 

also in the 

menu bar

 (see Figure 4.1). 

 
Further  information  regarding  the  monitoring  procedure  and  the  information  provided  in 
each window can be consulted in the LinkBoxMB Manual. 
 

 

 
 
 

 
 

 

Summary of Contents for Intesis INMBSMHI048O000

Page 1: ...Mitsubishi Heavy Industries Air Conditioning Gateway for integration of Mitsubishi Heavy Industries air conditioning systems into Modbus RTU and TCP systems USER MANUAL Issue date 05 2012 r1 0 ENGLISH...

Page 2: ...tive purposes and are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the...

Page 3: ...U All rights reserved This information is subject to change without notice URL https www intesis com 3 26 Gateway for integration of Mitsubishi Heavy Industries air conditioning systems into Modbus RT...

Page 4: ...ndoor units 10 IntesisTM Device Connections 11 Connect to Mitsubishi Heavy Industries Interface 12 Connect to Modbus Interface 12 3 2 1 Connect to Modbus RTU 12 3 2 2 Connect to Modbus TCP 13 3 2 3 Co...

Page 5: ...Modbus master read and write in the Modbus registers Moreover IntesisTM includes all hardware required to manage control Mitsubishi Heavy Industries indoor units without extra components needed Integ...

Page 6: ...response of a certain device is detected the corresponding virtual signal inside the gateway will be activated indicating communication error between the gateway and that precise device see 0 When a...

Page 7: ...revious Superlink or Superlink II New Superlink Indoor Unit actual address range is 00 to 47 INMBSMHI128O000 Model supporting up to 128 indoor units For Superlink II New Superlink Indoor Unit actual a...

Page 8: ...ts are always expressed in MSB LSB Bid Endian Modbus error codes are fully supported they will be sent whenever a non valid Modbus action or address is required see section 9 Modbus RTU Baud rate can...

Page 9: ...W SetPoint Temperature Celsius value 16 C to 30 C 5 R W Fan Speed 0 Low 1 Medium 2 High 3 Powerful 6 R W Remote Controller Lock Unlock 0 Remote Controller Locked 1 Remote Controller Unlocked 7 R W Lou...

Page 10: ...Communication Status 2542 R W Indoor Unit On Off 2543 R W Operation Mode 2544 R W SetPoint Temperature 2545 R W Fan Speed 2546 R W Remote Controller Lock Unlock 2547 R W Louver Control 2548 R Room Te...

Page 11: ...ce connector s description 1 Modbus RTU master EIA485 C1 8 Reset button Non supported 2 Modbus RTU master EIA232 C2 9 Superlink selector SLK New Superlink II Old Superlink I 3 Console serial port EIA2...

Page 12: ...ring with the power line should be avoided Select the appropriate Superlink mode in the SLK selector If you are using latest Air Conditioner of the Mitsubishi Heavy Industries network New Superlink se...

Page 13: ...A232 cable pin assign Cable 2 wire EIA485 TX RX TX RX TX RX TX RX Table 3 4 EIA485 cable pin assign To check connectivity and correct functioning use LinkBoxMB software see LinkBoxMB User Manual 3 2 2...

Page 14: ...o PC LinkBoxMB Connect the IntesisTM device to the PC serial port using the serial cable provided One end should be connected to the Console EIA232 port of the IntesisTM device see Figure 3 1 and the...

Page 15: ...ishi Heavy Industries indoor unit s integration to Modbus networks will be covered Connections configuration To configure the IntesisTM s connection parameters and to see the points list press on the...

Page 16: ...eave it blank if no router is needed 5 Port Enter the TCP port to use default for Modbus TCP is 502 6 Timeout Keep Alive Enter the time expressed in seconds that IntesisTM will wait upon no TCP activi...

Page 17: ...tting up 128AC for INMBSMHI128O000 48AC for INMBSMHI048O000 3 Timeout response Maximum amount of time permitted before activating the Communication Error signal It is expressed in milliseconds ms and...

Page 18: ...ues Possible values for the signal See section 2 5 for further detail on address mapping and the possible values on each signal Sending the configuration to IntesisTM When the configuration is finishe...

Page 19: ...s window shows all signals active within the gateway with its main configuration parameters and its real time value1 in the Value column Figure 4 6 LinkBoxMB Signals Viewer The signals viewer can be u...

Page 20: ...the values configured through the Connection tab in IntesisTM configuration MHI LBOX Binary file created from the information in the files described above This is the file downloaded to the IntesisTM...

Page 21: ...etup program supplied for this and follow the instructions given by the Installation wizard 2 Install IntesisTM in the desired installation site For your convenience check external enclosure measures...

Page 22: ...aly Superlink communication failure Check Superlink cables and terminals connectors length of cables etc HOST Off Configuration error Download the binary file again see 4 3 PAC Off Communication error...

Page 23: ...rted TCP RTU EIA232 or EIA485 Modbus TCP configuration parameters IP address Subnet mask Default gateway address TCP port Modbus RTU configuration parameters EIA232 EIA485 Baud rate Parity Slave numbe...

Page 24: ...ject to change without notice URL https www intesis com 24 26 Mechanical Electrical characteristics 1 Device can be installed in any position 5 mm 195 mm 138 mm 10 mm 15 mm Figure 7 1 External dimensi...

Page 25: ...ivity LNK ACT 4 x MHI Interface OP ERR HOST PAC Push buttons 1 x Reset Device Selectors 1 x SLK selector Console port EIA232 DB9 female DCE SELV Configuration Via console port 2 Firmware Allows upgrad...

Page 26: ...ase on power supply at primary side 33 E33 Inverter primary current error 35 E35 Cooling overload operation 36 E36 Discharge pipe temperature error 37 E37 Outdoor heat exchanger temperature thermistor...

Reviews: