HMS Networks INMBSBAC1000000 User Manual Download Page 25

11. Connections

Please find in the following table the gateway's ports and their use depending on the configuration.

Configuration

Port A EIA-485

Port B EIA-485

Port B EIA-232

Ethernet

IN-BAC-MBM

Modbus RTU

Bacnet MSTP, Modbus
RTU

NA

Modbus TCP, BACnet IP,
and Console*

IN-MBS-BAC

BACnet MSTP

Modbus RTU

Modbus RTU

Modbus TCP, BACnet IP,
and Console*

IN-ASCII-BAC

BACnet MSTP

ASCII

ASCII

BACnet IP, ASCII TCP, and
Console*

*Console: you can use the Ethernet port to connect the gateway to the PC for configuration purposes.

The following table shows the pinout correspondence for each serial port.

Port A EIA-485

Port B EIA-485

Pin-out

A4

B1

B-

A3

B2

A+

A1 and A2

B3

SNGD

11.1. Power Supply

NOTE

The way to supply power to the gateway is the same for all applications.

IMPORTANT

• Only use NEC class 2 or limited power source (LPS) and SELV-rated power supply.
• A wrong connection may cause earth loops that can damage the Intesis gateway and/or any other

system equipment.

• If using a DC power supply:

IMPORTANT

– Observe polarity on the power connection.
– Ensure the voltage applied is within the admitted range (see

Technical Specifications (page 33)

).

• If using an AC power supply:

IMPORTANT

– Ensure the voltage applied is 24 Vac (+/- 5%).
– Ensure the same power supply is not powering any other device.
– Do not connect any of the terminals of the AC power supply to earth.

Once connected, the Run LED of the gateway will turn on.

Connections

IN700-485 Series

USER MANUAL Version 1.0

Page 21 of 36

Summary of Contents for INMBSBAC1000000

Page 1: ...IN700 485 Series INTESIS PROTOCOL TRANSLATOR WITH SERIAL AND IP SUPPORT USER MANUAL Version 1 0 Publication date 2022 10 27 ENGLISH...

Page 2: ...the wide range of possible applications of the product and because of the many variables and requirements associated with any particular implementation HMS Networks cannot assume responsibility or li...

Page 3: ...7 7 Gateway Capacity 8 8 BACnet Interface 9 8 1 General Description 9 8 2 BACnet Client 9 8 3 Description 9 8 4 Points Definition 11 8 5 BACnet Server 11 8 6 Description 11 8 7 BACnet IP 12 8 8 BACnet...

Page 4: ...ctions 28 12 Set up Process with the Configuration Tool 29 12 1 Prerequisites 29 12 2 Intesis MAPS Configuration and Monitoring Tool 29 12 2 1 Introduction 29 12 2 2 Template Selection 30 12 2 3 Conne...

Page 5: ...IN7004853K00000 INMBSBAC3K00000 INBACMBM3K00000 INASCBAC3K00000 PRODUCT NAME ORDER CODE DESCRIPTION INTESIS MAPS TEMPLATE APPLICATION IN700 485 IN700485xxx 0000 Intesis Protocol Translator with Seria...

Page 6: ...ed and communication must only be connected to networks with indoor wiring All communication ports are considered for indoor use and must only be connected to SELV circuits Disconnect power wires befo...

Page 7: ...ons NOTICE Remarkable Information 2 4 Terminology Some terms generalize specific nomenclature to clarify some explanations Term Description Intesis gateway Gateway General term for this device Applica...

Page 8: ...s while others highlight specific differences capacities or limitations In general terms you must have a BACnet Modbus or ASCII control and monitoring system on one side and a Modbus or BACnet install...

Page 9: ...ntrol and monitoring system reads and writes those stored points This is possible because inside the gateway all Modbus registers of the server devices are associated with BACnet objects This makes th...

Page 10: ...n its memory the values of the points that you previously configured to be read With the change of value COV system the gateway can also subscribe to configured BACnet points automatically receiving t...

Page 11: ...f view the gateway continuously polls the installation or devices storing in its memory the values of the points that you previously configured to be read On the other hand from the ASCII point of vie...

Page 12: ...rsion 250 version 600 version 1200 version 3000 version Type of BACnet devices Those supporting communication with BACnet IP and MSTP Maximum number of BACnet devices 256 Maximum number of Modbus Regi...

Page 13: ...er status information of the BACnet device Value objects are bidirectional Every object has different properties The most meaningful one is the Present_Value property which indicates the real value of...

Page 14: ...tus Multistate Output Present Value Multistate signal Multistate Value Present Value Multistate signal for example Working mode command Accumulator Present Value Loop Present Value Every signal is ide...

Page 15: ...Multistate Output MV Multistate Value LOOP Loop ACUM Accumulator IMPORTANT Please read the documentation of the BACnet devices you re willing to integrate to know their object types BACnet object ins...

Page 16: ...BACnet server side a readable and writable register can be a value object type etc NOTICE The configuration tool provides default templates that make this signals assignment process easier Also you o...

Page 17: ...o associate the gateway with a MAC address within the MSTP network segment Baud rates supported for MSTP line are 9600 19200 38400 76800 115200 or Autobauding autodetect Standard wiring guidelines for...

Page 18: ...st specify as Modbus register addresses those configured inside the gateway corresponding to the signals on the field device protocol 9 4 Functions Supported NOTICE This part is common for both Modbus...

Page 19: ...o TCP IP frames which allows faster communication and a longer distance between client and server devices in comparison with RTU communication over a serial line Another benefit is using common TCP IP...

Page 20: ...e Modbus TCP network Modbus RTU client or both IMPORTANT Other Modbus devices connected to the network communicating with the gateway must always be server devices The gateway supports communication w...

Page 21: ...nal is also available from the field device interface Function code Read func Write func 01 Read Coils 02 Read Discrete Inputs 03 Read Holding Registers 04 Read Input Registers 05 Write Single Coil 15...

Page 22: ...onfigured to send these spontaneous messages If it doesn t the new value will remain available in the gateway for a later poll of the ASCII system You can configure this behavior for every gateway poi...

Page 23: ...s directly set when selecting the current BACnet type object Type Analog Digital BACnet object Analog input Analog output Analog value Multistate input Multistate output Multistate value Loop Accumula...

Page 24: ...ous poll for the point ASCII_String vv r Where ASCII_String is the string indicating the point address inside the Intesis gateway is the character used to indicate where the point data starts vv is th...

Page 25: ...B1 B A3 B2 A A1 and A2 B3 SNGD 11 1 Power Supply NOTE The way to supply power to the gateway is the same for all applications IMPORTANT Only use NEC class 2 or limited power source LPS and SELV rated...

Page 26: ...ms for each Application Look for the appropriate diagram depending on your application Figure 4 BACnet server to Modbus client IN700 485 Series Connection Diagrams for each Application Page 22 of 36 U...

Page 27: ...Figure 5 Modbus server to BACnet client Connection Diagrams for each Application IN700 485 Series USER MANUAL Version 1 0 Page 23 of 36...

Page 28: ...Figure 6 ASCII server to BACnet client IN700 485 Series Connection Diagrams for each Application Page 24 of 36 USER MANUAL Version 1 0...

Page 29: ...mum distance of 1200 meters Maximum of 32 devices connected to the bus A termination resistor of 120 is needed at each end of the bus The gateway has an internal bus biasing circuit already incorporat...

Page 30: ...ffic on the used port is allowed through all LAN paths NOTE After powering up the Intesis gateway for the first time DHCP will be enabled for 30 seconds After that time if a DHCP server provides no IP...

Page 31: ...e characteristics of the standard EIA 485 bus Maximum distance of 1200 meters Maximum of 32 devices connected to the bus A termination resistor of 120 is needed at each end of the bus The gateway has...

Page 32: ...l you can configure and monitor the gateway NOTE If your computer has an Ethernet port you can also use the Ethernet port of the gateway to connect both USB port TIP You can connect a USB storage devi...

Page 33: ...iguration tool from https www intesis com products intesis maps Intesis MAPS is a Windows compatible software explicitly developed to monitor and configure Intesis gateways NOTE The following sections...

Page 34: ...nection Tab 1 On the Connection Type parameter select the way you connected the gateway to your PC Select IP if you are using the Ethernet port of the Intesis gateway IMPORTANT Make sure you have an i...

Page 35: ...to the gateway Follow these steps 1 Click the Send button a If the gateway is still factory set you will be prompted to save the project on your PC Once you save it the configuration is automatically...

Page 36: ...ction to Check the current hardware status of the gateway Save communication logs to a ZIP file for diagnostic purposes Get information on the gateway Reset the gateway Viewers Intesis MAPS provides s...

Page 37: ...le Pinout from a DTE device 1500VDC isolation from other ports except Port B EIA 485 1 x serial EIA 485 green plug in screw terminal block 3 poles A B SGND reference ground or shield 1500VDC isolation...

Page 38: ...14 Dimensions Figure 9 Gateway dimensions Figure 10 Space needed for connections IN700 485 Series Dimensions Page 34 of 36 USER MANUAL Version 1 0...

Page 39: ...This page is intentionally left blank...

Page 40: ...This page is intentionally left blank...

Reviews: