IMPORTANT
BACnet IP and BACnet MSTP communication can not be used simultaneously.
8.8. BACnet MSTP
When you choose BACnet MSTP (serial communication), you have to use the configuration tool to associate the
gateway with a MAC address within the MSTP network segment.
Baud rates supported for MSTP line are: 9600, 19200, 38400, 76800, 115200, or Autobauding (autodetect).
Standard wiring guidelines for EIA-485 apply to the BACnet MSTP line.
IMPORTANT
BACnet MSTP and BACnet IP communication can not be used simultaneously.
BACnet MSTP