92 (124)
Configure the
actual temperature
transaction:
5.
To add a second transaction, click
Add
.
6.
Select the transaction to configure.
7.
In the transaction sidebar, on the right side of the screen.
Enter values for the transaction settings.
Actual temperature transaction settings:
Setting
Value
Description
Transactio
name
Actual Temp
Give the transaction a name.
Modbus
transaction
Read Holding
Registers (3)
This register read the actual temperature from the temperature regulator to the
PLC.
Address
Address: 0
Register: 1
Address 0 is Register 1.
Quantity
1
The transaction will address one data object.
Update
mode
Cyclically
Default value, can not be changed.
Update time 1000 ms
The update cycle is 1000 ms.
Anybus
®
Communicator
™
User Manual
SCM-1202-152 1.10 en-US