98 (124)
Create Write Parameter (0x02)
The Communicator writes values delivered from the PLC to the My Drive node.
1.
Add an
Empty template
and select it.
2.
Name the template
Write parameter (0x02)
.
3.
In the Frame editor
Request
area, add six
frame fields
with the following settings:
Request frame fields
Frame field
Name
Bytes/Length
Type/
Checksum type
Endianess
Fixed field
Value (Hex)
Constant
Function code 1
Byte
N/A
Yes
N/A
Node address
Node ID
1
Byte
N/A
N/A
N/A
Constant
Index
2
Word (two
bytes)
Big-endian
No
Min 0
Max 1000
Constant
Sub index
1
Byte
N/A
No
Min 0
Max 255
Data
Data
2
Byte
N/A
Yes
N/A
Checksum
Checksum
2
CRC
N/A
N/A
N/A
4.
In the Frame editor
Response
area, add five
frame fields
with the following settings:
Response frame fields
Frame fields
Name
Bytes
Type/
Checksum type
Endianess
Fixed field
Value (Hex)
Constant
Function code 1
Byte
N/A
Yes
N/A
Node address
Node ID
1
Byte
N/A
N/A
N/A
Constant
Index
2
Word (two
bytes)
N/A
No
Min 0
Max 1000
Constant
Sub index
1
Byte
N/A
No
Min 0
Max 255
Checksum
Checksum
2
CRC
N/A
N/A
N/A
Anybus
®
Communicator
™
User Manual
SCM-1202-152 1.10 en-US