HKC HQ Series Installation, Operation & Maintenance Manual Download Page 19

HQ Series Quarter-turn Electric Actuator 

Installation Operation& Maintenance Manual 

Doc No. : HumG-HQ-21 Rev2 

Page  19 / 26 

Valve Automation Leader, HKC 

certain values defined as inputs while other values are outputs, such as current temperature or valve 
position. 

5.2.5.

 

Specification 

 

Communication Protocol : Modbus-RTU according to IEC 61158 and IEC 61784 

 

Topology : Line topology with termination 

 

Number of nodes : 32 nodes in each segment without repeater, with repeaters expandable to 247 

 

Number of repeaters : Max. 9 with signal refreshing 

 

Cable length : Max. 1.2 Km with Repeater 10 Km 

 

Transfer Mode : RS-485 

 

Transmission Medium : Twisted, shielded 2-Wire cable according to IEC 61158 

 

Bus Access : Polling between master and slaves (query response) 

 

Supported  Baud  Rates : 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 

 

Supported  Parity Bit : Odd, Even, None 

 

Supported  Stop Bit : 1, 2 

For more detail information, please refer to separate ModBus operation manual. –18 rev1] 

6. 

Wiring 

6.1.

 

Electrical Connections and Preliminary Test 

WARNING: [You must never do any welding work while the actuator is connected with electrical 

line.  If  an  electrical  shock  occurs  on  the  actuator,  it  makes  a  cause  of  serious  damage  to  the 

microprocessor of the actuator.----- 19 Rev0] 

 

When working in potentially explosive atmospheres, observe the European Standards EN 60079-14 

“Electrical  Installation  in  Hazardous  Areas”  and  EN  60079-17  “Inspection  and  Maintenance  of 

Electrical Installations in Hazardous Areas”. Work on the electrical system or equipment must only 

be carried out by a skilled electrician himself or by specially instructed personnel under the control 

and supervision of such an electrician and in accordance with the applicable electrical engineering 

rules. 

 

For cable entries that are not used, user or installer shall close by [Ex db IIC or Ex tb IIIC certified 

blanking element suitable for each type of protection, Ex db or Ex tb so that type of protection of 

the enclosure is maintained. ----- 17 Rev0] 

 

[Dust ignition proof enclosure! Use a damped cloth for equipment surface cleaning. --- 15 Rev1] 

 

[

Flame 

proof enclosure! ---17 Rev0] Treat cover with care. Gap surfaces must not be damaged in 

any way. Do not jam cover during fitting. 

 

[Dust  ignition  proof  enclosure!  It  may  be  charged  electrostatic  potential.  Therefore  it  shall  be 

installed  in  such  way  that  the  risk  from  electrostatic  discharge  and  propagation  brush  discharge 

caused by rapid flow of dust is avoided. --- 15 Rev.1] 

6.1.1.

 

For testing purposes, loosen the bolts on the actuator cover and remove the cover. 

6.1.2.

 

Make sure that the power supply voltage is in accordance with the data on the nameplate of the 
actuator. 

6.1.3.

 

[Pass cables through the cable glands: NPT 3/4” or M25 for Ex “db”, additionally NPT 3/4”,  M25 
and M20 with M30 insert which shall be only applied for Ex ”tb”. ----- 17 Rev0] 

6.1.4.

 

Connect wires according to the enclosed wiring diagram. 

6.1.5.

 

Manually move the valve to half-open position. Then electrically operate the actuator to fully open 
position and check if the motor rotates in correct direction; standards units are counter-clockwise to 
open. 

6.1.6.

 

Test the actuator and check whether the limit switches work correctly 

6.1.7.

 

After the testing, check that all cable glands are correctly tightened. Applicable cable glands should 
be selected to meet the application’s condition. It is recommended to use the grade of IP67 cable 
gland or higher in potentially explosive atmosphere. 

6.1.8.

 

Put carefully the cover on the body and tighten the bolts. 

6.1.9.

 

[Tightening torque of the cover bolts should be applied as below.  

Model 

Cover bolt size (mm) 

Tightening Torque 

Allowable range 

HQ-008/010 

M8 x 35 

12.5 Nm 

10 ~ 15 Nm 

HQ-015/020 

M10 x 50 

24.5 Nm 

20 ~ 30 Nm 

HQ-030~300 

M12 x 55 

42.0 Nm 

35 ~ 50 Nm 

LCU-B, LCU-C 

M8 x 35 

12.5 Nm 

10 ~ 15 Nm 

---------------- 20 r1] 

 

Summary of Contents for HQ Series

Page 1: ...G HQ 21 Rev2 Page 1 26 Valve Automation Leader HKC HQ Series Quarter turn Electric Actuator Installation Operation Maintenance Manual Address 26 Emtibeui 28 ro Siheung si Gyeonggi do 15119 Republic of Korea Tel 82 31 488 8266 Fax 82 31 488 8269 Home page www hkcon co kr email hkcon hkcon co kr ...

Page 2: ...ter Clockwise to Close Setting 9 4 6 Mechanical Travel Stop Adjustment 9 4 7 Setting Potentiometer Replacement and Setting 10 4 8 Current Position Transmitter CPT Optional 10 4 9 Proportional Control Unit 11 4 10 ac dc Multi board 16 Rev1 17 5 Apply for optional communication protocol 17 5 1 ProfiBus Controller PBC 17 5 2 ModBus Controller 18 6 Wiring 19 6 1 Electrical Connections and Preliminary ...

Page 3: ...actice will result in severe injury or death WARNING Refers to personal safety Alerts the user to potential danger Failure to follow warning notices could result in personal injury or death CAUTION Directs the user s attention to general precautions that if not followed could result in personal injury and or equipment damage Notes Highlighted information is critical to the user s understanding of ...

Page 4: ...MPa stainless steel Bolts type M5 0 8 M6 1 M8 1 25 M10 1 5 M12 1 75 Tolerance Fit 6g 17 rev0 Cable connection Refers to the Appendix Ⅱ Wiring Diagram For cable entries or conduit entries that are not used user or installer shall close by certified blanking elements stopping plugs so that the flameproof or dust ignition proof properties of the enclosure are maintained Always ground the enclosure in...

Page 5: ... 6 7 3 5 3 4 3 2 3 1 3 2 1 5 1 1 1 8 1 0 1 7 0 9 50 49 5 75 HQ 300 300 112 93 65 NA 7 2 7 6 6 5 6 9 3 1 3 3 2 8 3 0 2 9 1 5 1 1 1 8 1 0 1 7 0 9 50 49 5 75 HQ 350 350 39 33 75 NA 24 9 19 2 22 6 17 4 12 4 9 5 11 2 8 7 11 2 4 2 3 0 3 8 2 6 3 6 2 5 40 42 75 HQ 400 400 58 49 75 NA 24 9 19 2 22 6 17 4 12 4 9 6 11 2 8 7 11 3 4 2 3 0 3 8 2 6 3 6 2 5 40 42 75 HQ 600 600 78 66 110 NA 16 3 11 6 14 8 10 5 9 9...

Page 6: ...d duty cycle may cause thermal overload Note 1 Type of duty according to VDE 0530 IEC 60034 1 Short time duty S2 Intermittent duty S4 The operation time at a constant load is short so that thermal equilibrium is not reached The pause is long enough for the machine to cool down to ambient temperature Example the duration of the short time operation is limited to 15min 15 Rev0 The duty is a sequence...

Page 7: ...Q 008 HQ 080 Note HQ 008 HQ 010 does not contain torque switch assembly 4 Installation 4 1 Pre installation 4 1 1 Use in general service Verify the actuator s nameplate to ensure correct model number torque output operating speed voltage and enclosure type before installation or use It is important to verify that the torque output of the actuator is appropriate for the torque requirements of the v...

Page 8: ...c actuator catalogue Refer to the CI 3 in this manual 4 2 Actuator Mounting Note Prior to mounting the part turn actuator must be checked for any damage Damaged parts must be replaced by original spare parts 4 2 1 Mounting is most easily done with the valve shaft pointing vertically upward But mounting is also possible in any other position the actuator may be mounted in any position 4 2 2 The HQ ...

Page 9: ...etting 4 4 1 Torque spring which detects the variation of torque during the operation is installed to prevent damaging the valve and actuator under overload condition Once the actuator is under overload the torque switch trips and the actuator stops immediately 4 4 2 The torque switches are set by manufacturer on the production site If re setting is necessary please contact the HKC service represe...

Page 10: ...lows 4 7 1 Manually rotate the hand wheel of the actuator to fully closed position 4 7 2 While measuring the resistance between P1 and P2 gently rotate the Potentiometer Gear until it reaches between 80 120 Ω 100 Ω preferred 16Rev1 4 7 3 Engage the Potentiometer Gear into the Point Shaft Gear and use an L wrench to tighten the screw Delete Danger 16 Rev1 4 8 Current Position Transmitter CPT Option...

Page 11: ... When the actuator is in the fully closed position adjust the ZERO dial on the CPT board until a reading of 4mA is achieved Apply power or use the manual override to drive the actuator to its fully open position counter clockwise rotation When the actuator is in the fully open position adjust the SPAN dial on the CPT board until a reading of 20mA is achieved 4 9 Proportional Control Unit Never wel...

Page 12: ...8 0 2 step Step10 15 5 7 5 0 5 step 0 4 7 5 It can be set in 16 step Step 0 4 0 4 0 8 0 1 step Step 5 9 1 1 8 0 2 step Step10 15 5 7 5 0 5 step Fault mode Fail close Fail open Fail stop Position conversion accuracy 0 2 to 5 may vary depending on conditions Ambient temperature 25 to 80 Ambient humidity 90 RH max non condensing condition Dielectric strength 1500V ac 1 minute 500V ac 1 minute Insulat...

Page 13: ...tep A F increase 0 5 increment per step 5 0 7 5 Initial setting is 4 If the setting value is too low the actuator may not be found the target point and it may be repeatedly operated in forward or reverse direction This is called Hunting and the user must appropriately adjust the deadband to avoid from the hunting Continuous hunting causes a failure of the actuator parts such as motor PCU board pot...

Page 14: ...ny button of ZERO SPAN ASCAN during the auto setting processes the auto setting mode will be cancelled 4 9 8 Fail close FC fail open FO and fail stop Dip Switch PCU model Power source SW3 PCU EB V1 5D for AC SW1 PCU DC V2 1C for DC When an analogue command signal does not come in or a wrong signal is received the PCU board will detect the Fault and operates actuator automatically in open close and...

Page 15: ...nd Red LED will be ON setting completed Wait until only the Green LED flickers after both Red and Green LED flicker for about 1 5 second Turn down No 4 of the dip switch I S input set to finish the setting If No 4 switch of the dip switch is turned down during setting the setting will be cancelled If there is no input for 2 minutes the setting process will also be cancelled 4 9 12 Adjust output fe...

Page 16: ...ode 4 9 14 LED display Operating display Status LED Color Display Function Open Red On Fully opened Flicker Moving to open position Auto Blue On Power on Flicker Auto setting Close Green On Fully closed Flicker Moving to close position Fault Yellow On Manual mode Flicker Malfunction Error display on the PCU EB V1 5D board for AC PCU EB V1 5D board for AC indicates an error condition when the yello...

Page 17: ...input switch As using for ac mode 1 switch on 2 switch off As using for dc mode 1 switch off 2 switch on 16 Rev1 NOTE Don t turn on both switch 1 and 2 at the same time that become a reason of damage of the board Motor terminal block Red wire of motor to connect 1 Black wire of motor to connect 2 16 Rev1 5 Apply for optional communication protocol 5 1 ProfiBus Controller PBC 5 1 1 ProfiBus Control...

Page 18: ... Slave Module MBRSM Positioned at level 7 of the OSI model MODBUS is an application layer messaging protocol that provides client server communication between devices connected on different types of buses or networks 5 2 2 As a MODBUS Serial Line protocol MODBUS RTU Remote Terminal Unit is a Master Slave protocol which takes place at level 2 Data Link layer of the OSI model The master initiates th...

Page 19: ...er shall close by Ex db IIC or Ex tb IIIC certified blanking element suitable for each type of protection Ex db or Ex tb so that type of protection of the enclosure is maintained 17 Rev0 Dust ignition proof enclosure Use a damped cloth for equipment surface cleaning 15 Rev1 Flame proof enclosure 17 Rev0 Treat cover with care Gap surfaces must not be damaged in any way Do not jam cover during fitti...

Page 20: ...Gap surfaces must not be damaged or dirtied in any way Do not jam the cover during fitting 7 2 Tools 7 2 1 Metric Allen Key Hex Wrench 1 7 2 2 Screw Driver 1 7 2 3 Metric Spanner 1 7 2 4 Wrench 200mm 1 7 2 5 Wrench 300mm 1 7 2 6 Wire Stripper Long Nose 1 7 2 7 Multi meter ac dc resistance 1 7 2 8 In case of PCU A D Board Option dc Signal Generator 4 20mA dc 1 7 2 9 In case of PCU CPT Board Option ...

Page 21: ...st ignition proof enclosure It may be charged electrostatic potential Therefore it shall be installed in such way that the risk from electrostatic discharge and propagation brush discharge caused by rapid flow of dust is avoided 15 Rev 1 CAUTION A regular inspection and maintenance should be performed by qualified and trained personnel Treat cover with care Gap surfaces must not be damaged or dirt...

Page 22: ...ept HQ 050 HQ 300 8 24 V ac dc Except HQ 050 HQ 300 9 12V dc Except HQ 015 HQ 300 A 12V ac dc Except HQ 015 HQ 300 c Option 1 Control Unit 0 without control unit 1 ICU Intelligent Digital Control Unit LCU C IMS Auto Phase Discriminator 2 SICU Semi Integral Control Unit LCU B IMS Phase Protect Indicator 3 RBP Rechargeable Battery Backup this option excludes from explosion proof 17 Rev0 4 IMS Integr...

Page 23: ...e Manual Doc No HumG HQ 21 Rev2 Page 23 26 Valve Automation Leader HKC Appendix II Wiring Diagram HQ 008 010 Standard 1Ph HQ 008 010 Standard DC DANGER HAZARDOUS VOLTAGE No electrical power should be connected until all wiring and limit switch adjustments have been completed ...

Page 24: ...ntenance Manual Doc No HumG HQ 21 Rev2 Page 24 26 Valve Automation Leader HKC HQ 015 300 Standard 1Ph HQ 015 300 Standard 1Ph PCU 17 Rev1 DANGER HAZARDOUS VOLTAGE No electrical power should be connected until all wiring and limit switch adjustments have been completed ...

Page 25: ...25 26 Valve Automation Leader HKC HQ 015 030 Standard DC HQ 015 030 Standard DC PCU 17 Rev1 DANGER HAZARDOUS VOLTAGE No electrical power should be connected until all wiring and limit switch adjustments have been completed NOTE Each actuator is packed with individual box and you can get the wiring diagram inside ...

Page 26: ...e Automation Leader HKC Appendix III Grounding HQ 008 010 HQ 015 and bigger size 19 Rev0 HKC Co Ltd 26 Emtibeui 28 ro Siheung si Gyeonggi do 15119 Republic of Korea Head Office Plant Tel 82 31 488 8266 Fax 82 31 488 8269 Fax Overseas sales office 82 31 488 9622 Domestic sales office 82 31 319 8267 Website www hkcon co kr ...

Reviews: