HK Instruments RHT-MOD Series Installation Instructions Download Page 3

Copyright HK Instruments 2021

www.hkinstruments.fi

Installation version 7.0 2021

CAUTION!

•  For CE compliance, a properly grounded shielding cable is 

required.

•  Use copper wire only. Insulate or wire nut all unused leads.
•  Supply a separate cable for relay and signal out when using line 

voltage to power the relay.

•  Any wiring may carry the full operating line voltage current based 

on field installation. The cover locking screw must be installed if 
the line voltage is supplied to the relay.

•  Care should be used to avoid electrostatic discharge to the device.
•  This unit has configuration jumpers. You may need to reconfigure 

this device for your application.

1) Route the cables through the square opening in the back plate or 

for surface wiring select a knockout on the top or bottom of the 
wall plate, as shown in Figure 2a.

2) Connect the wires as shown in Figure 2b and 2c.

STEP 3: CONFIGURATION

WIRING DIAGRAMS 

CONTINUED

Figure 2a - Routing the cables

24 V
GND
A
B
Analog 

+

Output 0/2–10 V / 4–20 mA

output 

Figure 2b - Wiring diagram: Power input & signal output

Wires can be routed through the square opening in the back plate

Wires can be routed through the top knockouts

Wires can be routed through the bottom knockouts

NC
COM
NO

STEP 2: WIRING DIAGRAMS

Figure 2d - Wiring diagram: Relay

NOTE! When using long connection wires it may be necessary to use a
separate GND wire for voltage output current to prevent measurement dis-
tortion. The need for an extra GND wire depends on the cross section and 
length of the used connection wires. If long and/or small cross section wires 
are used, supply current and wire resistance may generate a voltage drop in 
the common GND wire resulting in a distorted output measurement.

24 V
GND
A
B

+

Analog

Output 0/2...10 V

V

output

Figure 2c - Wiring diagram: Extra GND wire

Configuration of the RHT-MOD series device consists of:
1) Configuring the jumpers (see step 4)
2) Configuration menu options. (Display versions only. See the 

user manual for further details)

STEP 4: Jumper settings

          (Grey colour indicates that a jumper is installed)

No jumper

Circuit open

Jumper installed

Circuit closed

Jumper stored

Figure 3 - Jumper installation

1) Configuration of the output modes:

Select the output mode, current (4–20 mA) or voltage (0–10 V),
by installing jumpers as shown in Figure 4.
To select 2–10 V output mode on a display version of the device: 
First, select 0–10 V output by jumper, then change the voltage (V) 
output from 0–10 V to 2–10 V via the configuration menu. Please 
see the user manual for more details.

Summary of Contents for RHT-MOD Series

Page 1: ...SPECIFICATIONS Performance Measurement ranges Temperature 0 50 C Relative humidity 0 100 Accuracy Temperature 0 5 ºC Relative humidity 2 3 at 0 50 C and 10 90 rH Total error band includes accuracy hysteresis and temperature effect over 5 50 C and 10 90 rH Technical Specifications Media compatibility Dry air or non aggressive gases Measuring units C and rH Measuring element Temperature Integrated R...

Page 2: ...t in an area with good ventilation and an average temperature where it will be responsive to changes to the room conditions The RHT MOD should be mounted on a flat surface Do not locate the RHT MOD where it can be affected by Direct sunlight Drafts or dead areas behind doors Radiant heat from appliances Concealed pipes or chimneys Outside walls or unheated uncooled areas 2 Use the device as a temp...

Page 3: ...outs Wires can be routed through the bottom knockouts NC COM NO STEP 2 WIRING DIAGRAMS Figure 2d Wiring diagram Relay NOTE When using long connection wires it may be necessary to use a separate GND wire for voltage output current to prevent measurement dis tortion The need for an extra GND wire depends on the cross section and length of the used connection wires If long and or small cross section ...

Page 4: ...on code 04 Read input register Register Parameter description Data Type Value Range 3x0001 Parameter for P controller 16 bit 0 3 1 rH 2 TE 3 MAX 3x0003 rH reading 16 bit 0 1000 0 0 100 0 3x0004 Temp reading 16 bit 0 500 0 0 50 0 C 3x0007 rH high limit 16 bit 100 1000 10 0 100 0 3x0008 rH low limit 16 bit 0 900 0 0 90 0 3x0009 TE high limit 16 bit 50 500 5 0 50 0 C 3x0010 TE low limit 16 bit 0 450 ...

Reviews: