SCHEMATICS

DIMENSIONAL DRAWINGS

INSTALLATION

STEP 1: MOUNTING THE DEVICE

1) Mount the device in the desired location (see step 1).
2) Route the cables and connect the wires (see step 2).
3) The device is now ready for configuration.

 

 WARNING! Apply power only after the device is properly wired.

Figure 1a - Surface mounting

1) Select a mounting location on the wall at 1.2–1.8 m (4–6 ft) above 

the floor and at least 50 cm (20 in) from the adjacent wall. Do 
not block device air vents from any direction and leave atleast 
20 cm (8 in) gap to other devices. Locate the unit in an area with 
good ventilation and an average temperature, where it will be 
responsive to changes to the room conditions. The RHT-MOD 
should be mounted on a flat surface.

Do not locate the RHT-MOD where it can be affected by:
•  Direct sunlight
•  Drafts or dead areas behind doors
•  Radiant heat from appliances
•  Concealed pipes or chimneys
•  Outside walls or unheated / uncooled areas

2) Use the device as a template and mark the screw holes.
3) Mount the wall plate with screws.
•  Incorrect installation may cause a shift in temperature output
•  Secure the lid with a locking screw, if the relay is connected to the 

mains power

Display locking

jumper

Jumpers

Contact pins for

relay terminal

Contact pins for

terminal block

Terminal block

Terminal block for relay

99.0

90.0

83.0

49.5

14.0

45.0

18.0

Ø 4.0

32.0

YES

NO

NO

Figure 1b - Mounting orientation

Summary of Contents for RHT-MOD Series

Page 1: ...SPECIFICATIONS Performance Measurement ranges Temperature 0 50 C Relative humidity 0 100 Accuracy Temperature 0 5 ºC Relative humidity 2 3 at 0 50 C and 10 90 rH Total error band includes accuracy hysteresis and temperature effect over 5 50 C and 10 90 rH Technical Specifications Media compatibility Dry air or non aggressive gases Measuring units C and rH Measuring element Temperature Integrated R...

Page 2: ...t in an area with good ventilation and an average temperature where it will be responsive to changes to the room conditions The RHT MOD should be mounted on a flat surface Do not locate the RHT MOD where it can be affected by Direct sunlight Drafts or dead areas behind doors Radiant heat from appliances Concealed pipes or chimneys Outside walls or unheated uncooled areas 2 Use the device as a temp...

Page 3: ...outs Wires can be routed through the bottom knockouts NC COM NO STEP 2 WIRING DIAGRAMS Figure 2d Wiring diagram Relay NOTE When using long connection wires it may be necessary to use a separate GND wire for voltage output current to prevent measurement dis tortion The need for an extra GND wire depends on the cross section and length of the used connection wires If long and or small cross section ...

Page 4: ...on code 04 Read input register Register Parameter description Data Type Value Range 3x0001 Parameter for P controller 16 bit 0 3 1 rH 2 TE 3 MAX 3x0003 rH reading 16 bit 0 1000 0 0 100 0 3x0004 Temp reading 16 bit 0 500 0 0 50 0 C 3x0007 rH high limit 16 bit 100 1000 10 0 100 0 3x0008 rH low limit 16 bit 0 900 0 0 90 0 3x0009 TE high limit 16 bit 50 500 5 0 50 0 C 3x0010 TE low limit 16 bit 0 450 ...

Reviews: