Continuing from the step 4-4, 4-7, or 4-19.
The gain feature is designed to allow modification 
to the reported output, to match test and balance 
measurements, if necessary. The number shown 
is a multiplier. Increase the reported output by 
increasing the gain number above 1.000. To 
increase reported output by 5 %, adjust number 
to 1.050. Decrease the reported output by 
decreasing the gain number to less than 1.000. 
To decrease the reported output by 5 %, adjust 
number to 0.950.

Display

 

GAIN

1.000

1) Highlight submenu, the display will show 

GAIN

 and the number 

1.000

 will be blinking.

2) Cycle up or cycle down to increase or decrease the value of the 

multiplier.

3) Confirm selection when the correct value is shown on the display.
4) Cycle down to the next step in configuring the device. For the 

next configuration step in these installation instructions, go to 
step 4-9.

STEP 4-8: GAIN

Continuing from the selection of gain multiplier.

1) Highlight submenu, the display will show 

PRESS. UNIT

 and 

“WC

 will be blinking.

2) Cycle up or cycle down to select the correct 

measurement unit.

3) Confirm selection by tilting joystick 1 when the 

correct option is shown on the display.

4) Cycle down to the next step in configuring 

the device. For the next configuration step in 
these installation instructions, go to step 4-10.

Display

Pressure unit

output options

Pa

kPa

mbar

psi

inWC

mmWC

None

Menu

STEP 4-9: PRESSURE UNIT

 

PRESS.UNIT

“WC

Continuing from the selection of the pressure 
unit.

This device supports pressure output maximum 
settings to improve resolution of the pressure 
reading by limiting the range/span. Range/
span maximums are outlined in the table below. 
Range/span minimums are 0 for all units.

Display

 

P OUTPUT MAX

4.000“WC

STEP 4-10: PRESSURE OUTPUT MAX

Pressure unit

DPT-Flow Series-4 model number

DPT-Flow-4

DPT-Flow-8

DPT-Flow-20

DPT-Flow-30

Pa

100–1,000

200–2,000

500–5,000

700–7,000

kPa

0.1–1.0

0.2–2.0

0.5–5.0

0.7–7.0

mbar

1–10

2.0–20

5.0–50

7.0–70

mmWC

10–100

20–200

50–500

70–700

inWC

0.4–4.0

0.8–8.0

2.0–20

2.5–30

Pressure output

Upper range/maximum settings

Example:

 The DPT-Flow-4 has a capable range of 0–4.0 inWC. 

If pressure readings are expected below 2.50 inWC, adjust the 
pressure output maximum to 2.50 inWC to improve the resolution. 
The range/span will be adjusted to 0.0–2.50 inWC. The DPT-Flow-4 
can have the pressure output maximum set between 0.4–4.0 to 
improve resolution.

1) Highlight submenu, the top line of the display will show 

OUTPUT MAX

 and the bottom line will change to a blinking 

number equal to the maximum output.

2) Cycle up or cycle down by tilting joystick 2 or 3 respectively to 

increase or decrease the value shown on the display.

3) Confirm selection when the correct value is shown on the 

display.

4) Cycle down to the next step in configuring the device. For the 

next configuration step in these installation instructions, go to 
step 4-11.

Continuing from the selection of the pressure 
output maximum.

1) Highlight submenu, the display will show 

FLOW UNIT

 and 

m

3

/s

 will be blinking.

2) Cycle up or cycle down to select the correct 

flow unit.

3) Confirm selection by tilting joystick 1 when the 

correct option is shown on the display.

4) Cycle down to the next step in configuring 

the device. For the next configuration step in 
these installation instructions, go to step 4-12.

Display

Flow units

Volume

  m

3

/s

  m

3

/h

  CFM

  l/s

Velocity

  m/s

  FPM

Menu

STEP 4-11: FLOW UNIT

 

FLOW UNIT

m3/s

Continuing from the selection of the duct height.

1) Highlight submenu, the display will show 

PROBE QTY

 and 

1

 will be blinking.

2) Cycle up or down by tilting joystick 2 or 3 

respectively, to increase or decrease the 
number of probes installed.

Display

 

PROBE QTY

1

3) Confirm selection when the correct value is shown on the display.
4) Cycle down to the next step in configuring the device. For the 

next configuration step in these installation instructions, go to 
step 4-8.

STEP 4-7: PROBE QUANTITY

Summary of Contents for DPT-Flow-4 Series

Page 1: ...0 to 95 rH non condensing Physical Case Dimensions 3 54 x 3 74 x 1 4 90 0 x 95 0 x 36 0 mm Weight 5 3 oz 150 g Mounting 2 each 11 64 4 3 mm screw holes one slotted Materials Case ABS UL 94 V 0 Approved Lid PC UL 94 V 1 Approved Protection standard IP54 NEMA3 Display required for configuration 2 line display 12 characters line Size 1 81 W x 0 57 H 46 0 x 14 5 mm Electrical connections 4 screw termi...

Page 2: ... holes 3 Mount with appropriate screws not included MOUNTING THE DEVICE CONTINUED STEP 2 WIRING DIAGRAMS For CE compliance a properly grounded shielding cable is required 1 Unscrew the strain relief and route the cable s 2 Connect the wires as shown in figure 2 3 Tighten the strain relief Figure 2 Wiring diagram V Out P Out 24V GND Power Supply 24VDC 24VAC V A V A Output 0 10V 4 20mA Output 0 10V ...

Page 3: ...ick 1 will select and store that value Joystick 2 UP Cycle up Tilting joystick 2 will cycle up through the menu or submenu choices If you cycle past your desired choice the menu cycles through all the choices and return to the beginning of the list Joystick 3 DOWN Cycle down Tilting joystick 3 will cycle down through the menu or submenu choices If you cycle past your desired choice the menu cycles...

Page 4: ...onfiguring the device For the next configuration step in these installation instructions If Round is selected go to step 4 4 If Rectangle is selected go to step 4 5 Display Select duct Round inch Round mm Rectangle inch Rectangle mm Menu STEP 4 3 SELECT DUCT STEP 4 4 DUCT DIAMETER SEL PROBE Probe SEL DUCT Round inch Continuing from the selection of Round inch or Round mm 1 Highlight submenu the to...

Page 5: ...PT Flow 8 DPT Flow 20 DPT Flow 30 Pa 100 1 000 200 2 000 500 5 000 700 7 000 kPa 0 1 1 0 0 2 2 0 0 5 5 0 0 7 7 0 mbar 1 10 2 0 20 5 0 50 7 0 70 mmWC 10 100 20 200 50 500 70 700 inWC 0 4 4 0 0 8 8 0 2 0 20 2 5 30 Pressure output Upper range maximum settings Example The DPT Flow 4 has a capable range of 0 4 0 inWC If pressure readings are expected below 2 50 inWC adjust the pressure output maximum t...

Page 6: ... The device is now ready to be used Display SELECT EXIT MENU STEP 4 15 EXIT MENU Continuing from step 4 1 selection of the fan manufacturer 1 Determine if the fan manufacturer is included in the list of included fan manufacturers in the menu 2 Highlight submenu the display will show SEL FAN MFG and the menu of fan manufacturers If the fan manufacturer is included in the menu then 3a Cycle up or cy...

Page 7: ... s Pa Rosenberg 37 800 m3 h Pa Nicotra 10 1 500 m3 h Pa Comefri 10 2 000 m3 h Pa Ziehl Abegg 10 1 500 m3 h Pa ebm papst 10 1 500 m3 h Pa Gebhardt 50 4 700 m3 h Pa 1 k Q P Q k 2 P ρ Q k 2 P ρ Q k 2 P ρ Q k 2 P ρ Q k P Q k P Q Air volume in m3 s m3 h CFM l s k KVOL K value for air volume in flow unit pressureunit P Differential pressure measured by the FloXact probe ρ Density of the gas air in kg m3...

Page 8: ...anges to Products already purchased HK will give a new warranty for Products being replaced or repaired within the warranty period however only to the expiration of the original Product s warranty period The warranty includes the repair of a defective part or device or if needed a new part or device but no other costs except as otherwise stated in the HK Distributor Terms and Conditions The parts ...

Reviews: