OUTPUT SIGNAL CONFIGURATION
CONTINUED
STEP 4: CONFIGURATION MENU
Figure 3 - Jumpers
Terminal Block
Pressure
Sensor
LED
Joystick 1
Zero
V OUT
P OUT
24V
GND
4-20mA
Out
0-10V
Menu Buttons
Joystick 2
Flow
Joystick 3
Select
Up
Down
Pressure
Output
Jumpers
Flow
Pressure
4–20 mA
Out
0–10 V
Jumper
stored
Gray block indicates how the jumper is installed.
Figure 4 - Output signal 0–10 V or 4–20 mA
jumper positions
4–20 mA
Out
0–10 V
Flow
Pressure
Flow
Pressure
Flow
Pressure
Flow
Pressure
Jumpers
Jumpers
Jumpers
Jumpers
Gray colour indicates
that a jumper is
installed
Flow out: 0–10 V
Pressure out: 4–20 mA
Flow out: 0–10 V
Pressure out: 0–10 V
Flow out: 4–20 mA
Pressure out: 4–20 mA
Flow out: 4–20 mA
Pressure out: 0–10 V
4–20 mA
Out
0–10 V
4–20 mA
Out
0–10 V
4–20 mA
Out
0–10 V
Selection convention used to input information into DPT-Flow
Entering information into the DPT-Flow is accomplished with three
(3) joysticks (see schematics). The joysticks are labeled as follows:
Joystick 1 – SELECT
Tilting Joystick 1 serves two functions:
A.
Highlight submenus
: when a submenu is available, tilting
joystick 1 will activate the submenu, causing it to blink.
B.
Confirm selection
: when the proper choice is shown on the
screen, tilting joystick 1 will select and store that value.
Joystick 2 – UP
Cycle up:
Tilting joystick 2 will cycle
up
through the menu or
submenu choices. If you cycle past your desired choice, the
menu cycles through all the choices and return to the beginning
of the list.
Joystick 3 – DOWN
Cycle down:
Tilting joystick 3 will cycle
down
through the menu
or submenu choices. If you cycle past your desired choice, the
menu cycles through all the choices and returns to the beginning
of the list.
STEP 4-0: ENTER THE CONFIGURATION MENU
Tilt joystick 1 (see schematics for the location of the joysticks 1, 2
and 3) for 2-5 seconds to enter the configuration menu.
STEP 4-1: SELECT MODE
Determine if the configuration is for:
Fan manufacturer
where you will connect
tubing directly to the ports on the fan.
-or-
Probe
where you will connect tubing to a probe.
1) Highlight submenu by tilting joystick 1.
Fan
Mfg
will begin blinking.
2) Cycle up or cycle down by using joystick 2 or
joystick 3, between the submenu choices.
3) Confirm selection by tilting joystick 1 when the
correct choice is shown on the display.
SELECT MODE
Fan Mfg
Display
Select mode
Fan Mfg
Probe
Menu
If
Fan Mfg
is selected:
Cycle down by using joystick 3 to cycle to the next step in
configuring the device. For the next configuration step in these
installation instructions, go to step 4-16.
If
Probe
is selected:
Cycle down by using joystick 3 to cycle to the next step in
configuring the device. For the next configuration step in these
installation instructions, go to step 4-2.