HK Instruments CDT 2000 Duct Series Installation Instructions Download Page 3

Copyright HK Instruments 2017

www.hkinstruments.fi

Installation version 5.0 2017

STEP 3: CONFIGURATION

Configuration of the CDT2000 Duct series device consists of:
Configuration menu options. (Display versions only.) 
Press the select button to accept changes. Move to the next set

-

ting by pressing the down button.

1) Activate the device Menu by pushing the select button for 2 

seconds.

2) Select the CO

2

 low limit for output band: 0...1900 ppm.

For CE compliance a properly grounded shielding cable is
required.
1) Unscrew the strain relief and route the cable(s). 
2) Connect the wires as shown in figure 2a.
3) Tighten the strain relief.

CO

2

T

24 V
GND

+

Power Supply

24VDC / 24VAC

Output 0/2...5/10 V
Output 0/2...5/10 V

       

CO

2

 OUT MIN

  400 CO

2

 ppm

  

SELECT

UP

DOWN

3) Select the CO

2

 high limit for output band: 500...2000 ppm.

       

CO

2

 OUT MAX

  2000 CO

2

 ppm

  

SELECT

UP

DOWN

4) Select the temperature low limit for output band: 0...45.0 °C or 

32...112 °F.

       

TE OUT MIN

     0.0 °C

  

SELECT

UP

DOWN

5) Select the temperature high limit for output band: 5...50.0 °C 

or 42...122 °F.

6) Select the output maximum voltage: 5 V / 10 V.

       

TE OUT MAX

    50.0 °C

  

SELECT

UP

DOWN

       

MAX OUTPUT V

      10 V

  

SELECT

UP

DOWN

7) Select the output minimum voltage: 0 V / 2 V.

       

MIN OUTPUT V

       0 V

  

SELECT

UP

DOWN

8) Push the select button to exit menu.

  SELECT

 EXIT MENU

SELECT

STEP 2: WIRING DIAGRAMS

NOTE! When using long connection wires it may be necessary to use a 
separate GND wire for voltage output current to prevent measurement 
distortion. The need for an extra GND wire depends on the cross sec

-

tion and length of the used connection wires. If long and/or small cross 
section wires are used, supply current and wire resistance may gener

-

ate a voltage drop in the common GND wire resulting in a distorted 
output measurement.

CO

2

T

24 V
GND

+

Power Supply

24VDC / 24VAC

Output 0/2...5/10 V
Output 0/2...5/10 V

V

V

Figure 2a - Wiring diagram

Figure 2b - Wiring diagram: Extra GND wire

Summary of Contents for CDT 2000 Duct Series

Page 1: ...o to be unoccupied for four hours per day so that the indoor CO2 concentration drops to the outside level CDT2000 DC Duct is a dual channel model with a measuring channel and a reference channel that makes a continuous comparison and the necessary adjustment accordingly CDT2000 DC Duct is also suitable for buildings that are continuously occupied CDT2000 Duct series devices are commonly used to mo...

Page 2: ...e device as a template and mark the screw holes 3 Mount the flange on the duct with screws not included Figure 1a 4 Adjust the probe to the desired depth Ensure that the end of the probe reaches the middle of the duct Figure 1b 5 Tighten the screw on the flange to hold the probe in position Figure 1a Mounting a flange Figure 1b Mounting the probe in a flange Air flow direction Air flow direction Air...

Page 3: ...DOWN 4 Select the temperature low limit for output band 0 45 0 C or 32 112 F TE OUT MIN 0 0 C SELECT UP DOWN 5 Select the temperature high limit for output band 5 50 0 C or 42 122 F 6 Select the output maximum voltage 5 V 10 V TE OUT MAX 50 0 C SELECT UP DOWN MAX OUTPUT V 10 V SELECT UP DOWN 7 Select the output minimum voltage 0 V 2 V MIN OUTPUT V 0 V SELECT UP DOWN 8 Push the select button to exi...

Page 4: ... incorrect care or reconstruction or changes and instal lation work not done by the seller or his her authorized representative The selection of materials for devices prone to corrosion is the buyer s responsibility unless otherwise is legally agreed upon Should the man ufacturer alter the structure of the device the seller is not obligated to make comparable changes to devices already purchased A...

Reviews: