HK Instruments CDT 2000 Duct Series Installation Instructions Download Page 1

Copyright HK Instruments 2017

www.hkinstruments.fi

Installation version 5.0 2017

INSTALLATION

INSTRUCTIONS

CARBON DIOXIDE TRANSMITTERS

CDT2000 Duct Series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE 

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS 
DEVICE.

•  Failure to observe safety information and comply with 

instructions can result in PERSONAL INJURY, DEATH AND/OR 

PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect 

power before installing or servicing and use only wiring with 
insulation rated for full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered 

system whose specifications and performance characteristics 
are not designed or controlled by HK Instruments. Review 
applications and national and local codes to assure that the 
installation will be functional and safe. Use only experienced and 
knowledgeable technicians to install this device.

SPECIFICATIONS

Thank you for choosing an HK Instruments CDT2000 Duct series 
carbon dioxide transmitter. The CDT2000 Duct series is intended 
for use in commercial environments in HVAC/R applications.

The CDT2000 Duct series measures carbon dioxide (CO

2

), utilizing 

the industry standard NDIR measurement principle, and tempera

-

ture (T).  Illuminated display ensures easy readability also from a dis

-

tance. The CDT2000 Duct has a screwless lid and an easily adjust

-

able mounting flange that make the installation of the device easy.

The CDT2000 Duct series transmitters calibrate themselves auto

-

matically using ABC

TM

 logic. The ABC

TM

 logic requires that the space 

in which the transmitter is used needs to to be unoccupied for four 
hours  per  day  so  that  the  indoor  CO

2

  concentration  drops  to  the 

outside  level.  CDT2000-DC  Duct  is  a  dual  channel  model  with  a 
measuring channel and a reference channel that makes a continuous 
comparison and the necessary adjustment accordingly. CDT2000-
DC Duct is also suitable for buildings that are continuously occupied.

CDT2000 Duct series devices are commonly used to monitor:

•  CO

2

 levels of incoming and return air in ventilation system

• CDT2000-DC Duct series devices can also be used in applications 

where there is a constant source of carbon dioxide present (for 
example hospitals and greenhouses)

SPECIFICATIONS

Performance

Measurement ranges:

 

 

CO

2

: 400–2000 ppm

Temperature: 0...50 °

°F

 

32...122

 

/

C

Accuracy:

CO

2

: ±40 ppm + 2 % of reading, DC model: 75 ppm or 

10 % of reading (whichever is greater)

Temperature: <0.5 º

°F

 

<0.9

 

/

C

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Measuring units:

ppm and °C

Measuring element:

CO

2

: Non-dispersive infrared (NDIR)

Temperature: NTC10K

Calibration:

Automatic self-calibration ABC Logic

TM

 or continuous 

comparison (DC)

Environment:

Operating temperature: 0...50 °

 

°F

 

32...122

 

/

C

Storage temperature: -20...70 °

°F

 

-4...158

 

/

C

Humidity: 0 to 95 % rH, non condensing

Physical

Dimensions: 

Case: 119 x 100 x 44.7 m

 

1.76"

 

x

 

3.94

 

x

 

4.69

 

/

m

Probe: L=188 mm, d=12 m

d=0.47"

 

7.40",

L=

 

/

m

Mounting:

With flange, adjustable 0...188 mm

0...7.40"

 

/

 

Weight: 

150 

oz

 

5.30

 

/

g

Materials: 

Case: ABS

Cover: PC

Probe: ABS

Protection standard: 

IP54

Electrical connections:

4 spring loaded terminals

(24 V, GND, CO

2

, T)

0.2–1.5 mm

2

 (12–24 AWG)

Electrical

Supply voltage: 24 VAC or VDC ±10 %

Current consumption: max 230 mA (at 24 V) + 10 mA 

for each voltage output

Output signals for every media:

0/2...5/10 VDC, Load R minimum 1 kΩ

Conformance

Meets requirements for CE marking:

EMC Directive 2014/30/EU

RoHS Directive 2011/65/EU

WEEE Directive 2012/19/EU

INTRODUCTION

APPLICATIONS

WARNING

COMPANY WITH

MANAGEMENT SYSTEM

CERTIFIED BY DNV GL

= ISO 9001 = ISO 14001 =

RoHS 2

2011/65/EU

Summary of Contents for CDT 2000 Duct Series

Page 1: ...o to be unoccupied for four hours per day so that the indoor CO2 concentration drops to the outside level CDT2000 DC Duct is a dual channel model with a measuring channel and a reference channel that makes a continuous comparison and the necessary adjustment accordingly CDT2000 DC Duct is also suitable for buildings that are continuously occupied CDT2000 Duct series devices are commonly used to mo...

Page 2: ...e device as a template and mark the screw holes 3 Mount the flange on the duct with screws not included Figure 1a 4 Adjust the probe to the desired depth Ensure that the end of the probe reaches the middle of the duct Figure 1b 5 Tighten the screw on the flange to hold the probe in position Figure 1a Mounting a flange Figure 1b Mounting the probe in a flange Air flow direction Air flow direction Air...

Page 3: ...DOWN 4 Select the temperature low limit for output band 0 45 0 C or 32 112 F TE OUT MIN 0 0 C SELECT UP DOWN 5 Select the temperature high limit for output band 5 50 0 C or 42 122 F 6 Select the output maximum voltage 5 V 10 V TE OUT MAX 50 0 C SELECT UP DOWN MAX OUTPUT V 10 V SELECT UP DOWN 7 Select the output minimum voltage 0 V 2 V MIN OUTPUT V 0 V SELECT UP DOWN 8 Push the select button to exi...

Page 4: ... incorrect care or reconstruction or changes and instal lation work not done by the seller or his her authorized representative The selection of materials for devices prone to corrosion is the buyer s responsibility unless otherwise is legally agreed upon Should the man ufacturer alter the structure of the device the seller is not obligated to make comparable changes to devices already purchased A...

Reviews: