INSTALLING THE OUTDOOR UNIT

INSTALLER

BLEEDING

INSTALLER

8

Do not install the outdoor unit in pits or air vents

Installing the pipes

Use suitable connecting pipes and equipment for 

the refrigerant R410A.

Wrap all the refrigerant pipes and joints.
Tighten the connections using two wrenches wor-

king in opposite directions.

Vacuum pump

Humid air left inside the refrigerant circuit can cause com-

pressor malfunction. After having connected the indoor

and outdoor units, bleed the air and humidity from the

refrigerant circuit using a vacuum pump.
(1) Unscrew and remove the caps from the 2-way and 3-

      way valves.

(2) Unscrew and remove the cap from the service valve.

(3) Connect the vacuum pump hose to the service valve.

(4) Operate the vacuum pump for 10-15 minutes until an

      absolute vacuum of 10 mm Hg has been reached.

(5) With the vacuum pump still in operation, close the 

      low-pressure knob on the vacuum pump coupling.

      Stop the vacuum pump.

(6) Open the 2-way valve by 1/4 turn and then close it

      after 10 seconds. Check all the joints for leaks using

      liquid soap or an electronic leak device.

(7) Turn the body of the 2-way and 3-way valves. Discon-

      nect the vacuum pump hose.

(8) Replace and tighten all the caps on the valves.

Vacuum pump

Vacuum pump

Location

Twisting moment (N.m)

35-40
60-65
45-50
70-75

Φ12
Φ19

Diameter (mm) 

Φ9.52

Φ16

15-20

Φ6

18K unit need to be installed the indoor unit 

Caution: Installation Must be Performed in Accordance 

with the NEC/CEC by Authorized Personnel Only.

conversion joint

18K MODE:

INDOOR

UNIT

Connect to the

indoor unit

Refrigerant fluid di

rection of fiow

3-w

ay valve

2-w

ay valve

inlet

(2)Turn

(8) Secure

(7)Turn to open fully

(2)Turn

(8) Secure

(6) Open by 1/4 turn

(7)Turn to open fully

(2)Turn

(8) Secure

V

alve cap

Valve cap

Service

The refrigerant pipes must not exceed the maximum

Use bolts to secure the unit to a flat, solid floor.

When mounting the unit on a wall or the roof, make

sure the support is firmly secured so that it cannot

move in the event of intense vibrations or a strong

wind.

Install the drain fitting and the drain hose

(for model with heat pump only)

Condensation is produced and flows from the out-

door unit when the appliance is operating in the 

heating mode. In order not to disturb neighbours 

and to respect the environment,install a drain fitting 

and a drain hose to channel the condensate water.

Install the drain fitting and rubber washer on the 

outdoor unit chassis and connect a drain hose to it 

as shown in the figure.

Models(m)

18Kx2

Max. connection pipe length 20
Max. connection pipe length

(Simple one indoor unit)

10

The sum of the capacity codes of the indoor units should be 

among 50%-150% of that of the outdoor unit.

heights 5m.

Summary of Contents for ASE9U2I-HN

Page 1: ...ed Air Conditioner HOSM 18UIHN Thank you for choosing our product For proper operation please read and keep this manual carefully If you have lost the Owner s Manual please contact the local agent or...

Page 2: ...thout displayer the position and shape of the displayer please refer to the real one In line with the company s policy of continual product improvement the aesthetic and dimensional characteristics te...

Page 3: ...ectric shock Donot spray wateronindoorunit It may cause electric shock ormalfunction After removing the filter do not touch fins to avoid injury Do not use fire or hair dryer to dry the filter to avoi...

Page 4: ...Air switch should be included magnet buckle and heating buckle function it can protect the circuit short and overload Air Conditioner should be properly grounded Incorrect grounding may cause electric...

Page 5: ...and outdoor unit should be connected by a professional If the length of power connection wire is insufficient please contact the supplier for a new one Avoid extending the wire by yourself For the ai...

Page 6: ...turned on or off according to your requir ement automatically please do not turn on or turn off the unit freque ntly otherwise disadvantage effect may be caused to the unit Rated voltage of this air c...

Page 7: ...clean the air conditioner cabinet The temperature of refrigerant circuit will be high please keep the interconnection cable away from the copper tube Note The above figures are only intended to a simp...

Page 8: ...d unit B must be corresponding to each other respective Note the above figures are only intended to be a simple diagram of the appliance and may not correspond to the appearance of the units that have...

Page 9: ...p Location Twisting moment N m 35 40 60 65 45 50 70 75 12 19 Diameter mm 9 52 16 15 20 6 18K unit need to be installed the indoor unit Caution Installation Must be Performed in Accordance with the NEC...

Page 10: ...l Contact service center before installation to avoid the malfunction due to unprofessional installation When picking up and moving the units you must be guidedby trained and qualified person Do not u...

Page 11: ...its Have the length of refrigerating pipe and refrigerant charge amount been recorded Has the unit been safely grounded Problems Owing to Improper Installation The unit may drop vibrate or make noises...

Page 12: ...66129920519...

Reviews: