HT-100R Series
HITROL CO., LTD.
17
Cause
Checked
When the buoyancy has been lost because of
impurities between the FLOAT of the sensor and the
pipe
Clean the pipe and the FLOAT
When the sensor resistor has been burnt intensively
and massively, thereby causing short circuit, and the
FLOAT is located in that position
Replace the sensor PCB (The
output drastically rises or
drops when the FLOAT goes
out
of
the
position.
Measurement errors occur.)
When the sensor resistor has been burnt intensively
and massively and opened, and the FLOAT is located in
that position
Replace the sensor PCB (The
output drastically rises or drops
when the FLOAT goes out of the
position. Measurement errors
occur.)
Cause
Checked
In the process for the inter-element (diode) of the M-
100R to be damaged, temporary over-measurement
(approximately 10%) caused by over current and noise
outputs are formed.
Replace the M-100R