Overview               

 

 

 

 

 

Features 

 

 

 

 

 

 

 

 

 

Mechanism   

 

 

 

                                     

                             

 

 

 

 

 

 

■ The level of different types of liquid and power can be detected. 

■ It has a solid structure and is semi-permanent, because it does not have any   

mechanically moving part. 

■ Different shapes of probes are offered for different purposes. 

■ It can be used with a corrosive liquid (aqueous solution). 

■ Operation state can be checked. 

■ Output delay can be set. 

■ It has the pressure-resistant and ex-proof structure (ex. d IIC) (HPC-95R Series)

 

The  HCC(HPC)-95R  Series is  a  level  switch  to  detect an object  to  be  measured  in  a 

tank using its dielectric constant. It can be installed on the top or side of a tank, and it 

is  easy  to  adjust  and  use  with  corrosive  fluid,  making  it  applicable  to  different 

industries. 

 

 

When  the  level  between  the  electrode  probe  and  wall  increases,  the  air  around  electrode 

probe  is  replaced  with  another  dielectric  substance  (object  to  be  measured)  to  change  the 

capacitance value. Initially, the electrode probe has a low capacitance value in the air, but the 

value  increases  when  the  object  to  be  measured  rises  and  covers  the  electrode  probe.  This 

change is sensed to detect the object to be measured. 

C: Capacitance of object to be measured 

C1: Initial capacitance 

R: Conductivity of object to be measured 

 

Summary of Contents for HCC-95R Series

Page 1: ...R D INSTITUDE HITROL CO LTD 141 Palhakgol road Jori eup Paju si Gyeonggi do Korea TEL 00 82 31 950 9700 FAX 00 82 31 943 5600 www hitrol com INSTRUCTION MANUAL CAPACITANCE TYPE LEVEL SWITCH HCC 95R Se...

Page 2: ...onent and Technical Data 6 Attachment and Cautions 8 Wiring and AMP 9 Setting 9 Removal Cautions 10 Cautions for Inserted External Wire 10 Ex Proof Product Cautions for Grounding 10 Ex Proof Product S...

Page 3: ...t an object to be measured in a tank using its dielectric constant It can be installed on the top or side of a tank and it is easy to adjust and use with corrosive fluid making it applicable to differ...

Page 4: ...16L with TEFLON Process Connection PT 1 M Screw Housing Cable Entry AL PF3 4 F IP65 Ex Proof Version Model HPC 95R HPC 95RH HPC 95RW HPC 95RWH Probe Type Rod Rope Mounting Screw Flange Ambient Tempera...

Page 5: ...12V 6 Power State LED Green 7 Operating Temperature 20 70 8 Dimension 80mm x 65mm x 20mm 9 Weight 50g Combination Unit Model HLC 95R L HLC 95R P Installation Local Panel inside Ambient Temperature 20...

Page 6: ...Std NPT 1 PF 1 Other Flanges ANSI JIS DIN Tri Clamp Material 316L Other Active Rod material 316L With Teflon Weisht material C S 316L Housing Connection Probe High Temp Version High Temp Version Mater...

Page 7: ...it out website www hitrol com and download from Technical Data For Liquids For Solids Rod Probe Rod Probe Fully insulated TEFLON Rod Probe Rope Probe Total length L 100 2 500 300 1 000 100 2 500 Min 1...

Page 8: ...th low dielectric constant To install 2 or more level switches in one container keep 300m or more between probes If the gap is smaller between probes they may interfere each other causing instability...

Page 9: ...t Set Fail Safe Mode to H Turn on the power Set the Sensitivity Volume to the center and select range S W 10 90PF 65 150PF 120 260PF to place the Red LED On Off between the center and H of the Sensiti...

Page 10: ...ndings For the external grounding the ground wire must be 4 mm2 4 mm SQ An internal ground wire must have the same size as the power line The size of an internal grounding terminal lug must be 3 1 mm2...

Page 11: ...serial number working temperature working pressure and output The serial number is a unique manufacturing number Do not apply a non ex proof product in an ex proof zone An ex proof product can be use...

Page 12: ...1 Palhakgol road Jori eup Paju si Gyeonggi do Korea TEL 031 950 9700 Headquarters and A S FAX 031 943 5600 Headquarters and A S Inspection The sensor and transmission parts of a capacitive level trans...