![HITESCA CCHIA/CCHIBA 301 Nstallation, Operation And Maintenance Manual Download Page 13](http://html1.mh-extra.com/html/hitesca/cchia-cchiba-301/cchia-cchiba-301_nstallation-operation-and-maintenance-manual_2140083013.webp)
13
03.17 207529 Rev.100
CSTIA/CCHIA
– CSTIBA/CCHIBA
SPLIT HORITZONTAL INVERTER UNITS
AUTONOMOUS AIR-AIR
(1) Cooling Rated Conditions:
Temperatura Interior Seca: 27ºC, Temperatura Interior Húmeda: 19ºC
(2) Heating Rated Conditions:
Temperatura Interior Seca: 20ºC
(3) GWP:
Global warming potential (climatic) of 1 kg of greenhouse gas relative to 1 kg of CO
2
, calculated in terms of 100-year warming potential.
(4)
Only the outdoor
units which has serial “FLARE” valve (not from option) are charged with refrigerant, the rest come Pre-Charged with dry nitrogen.
CSTIA/CSTIBA
301
CAPACITIES
Rated Cooling Capacity (1)
kW
7,4
Cooling Capacity (20
– 100 – 120 Hz)
kW
1,2
– 7,4 – 8,1
Rated Heating Capacity (2)
kW
7,5
Heating Capacity (20
– 100 – 120 Hz)
kW
1,3
– 7,5 – 8,3
Coeficient EER
>8
SEER
4,6
Class
B
SCOP (Warm Zone)
4,1
Class
A+
Sound Power at Low Speed
dBA
34
Sound Power at Medium Speed
dBA
40
Sound Power at High Speed
dBA
50
REFRIGERANT
Type
R-410A
Global Warming Potential (GWP) (3)
2088
Frigorific Connection Liquid Line
“
3/8
Frigorific Connection Gas Line
“
1/2
Charge (4)
kg
-
DRAINAGE
Condensate Pump
YES
Available Pressure
mm. W.C.
400
INDOOR HEAT EXCHANGER
Type
Aluminum Fins and Copper Pipes
Frontal Surface
m
2
0,360
Fins Size
mm
2,1
Piping Diameter
mm
7,2
ELECTRICAL SPECIFCATIONS
Power Supply
V / fases / Hz
220-240 / I / 50
Electric Connections
mm²
2 x 1,5 + T
Interconnection with Termostat
BELDEN-8672
Twisted Pair + Shielded
Interconnection Between Units
BELDEN-8672
Twisted Pair + Shielded
INDOOR FAN
Diameter
mm
380
Voltage
V
220-240 / I / 50
Motor Power
kW
0,13
Transmission
AC Integrated Motor 3 Speeds
Rated Airflow
m
3
/h
840 / 1000 / 1200
DIMENSIONS AND WEIGHT
Length
mm
830
Width
mm
830
Height
mm
300
Weight
kg
31