10
03.17 207529 Rev.100
CSTIA/CCHIA
– CSTIBA/CCHIBA
SPLIT HORITZONTAL INVERTER UNITS
AUTONOMOUS AIR-AIR
OPERATION LIMITS
OUTDOOR AIR
INDOOR AIR
DRY
WET
DRY
WET
COOLING
ºC
ºC
ºC
ºC
Standard
35ºC
-
27ºC
19ºC
Minimum
18ºC
-
19ºC
15ºC
Maximum
48ºC
-
32ºC
23ºC
HEATING
ºC
ºC
ºC
ºC
Standard
7ºC
6ºC
20ºC
-
Minimum
-10ºC
-11ºC
20ºC
-
Maximum
24ºC
18ºC
27ºC
-
Units can operate at a maximum altitude of 1.500 meters.
For other conditions, please consult.
These units are designed to work with 100% recirculated air. The installation with 100% outdoor air is prohibited. See
application limits.
Main power supply of the unit should agree with the data shown on the nameplate. HITECSA will not be held
responsible for damages resulted from non observance of the above.
Always use the wiring diagram sent with the unit to make electrical connections
Check that the crankcase heater has been working at least 24 hours prior to the start-up of the unit.
Power supply should be within 10% of Volts indicated on the unit nameplate.
Do not operate the unit at different voltage from that shown on the unit nameplate.
The installer should put line protection elements in compliance with current legislation.
The interconnecting wires should be protected with a tube or put inside a groove channel.
Before starting installation, service or maintenance, turn off the main power switch in
order to avoid electrical shock that may cause personal damages.