CCHA/ECHA – CCHBA/ECHBA
Installation, operation and maintenance instructions
21
NOTES :
-
Refrigerant lines should be as short and straight as possible. Use recommended diameters
to reduce quantity of refrigerant in the system.
-
Fasten the tubes to fixed elements by means of braces to avoid vibration.
-
Carry out welding works in dry nitrogen atmosphere inside the line to be welded -USE A
BOTTLE WITH PRESSURE REGULATOR- to avoid the appearance of oxide and to expel rest of
polluting material or humidity. Use rods with a minimum 15% of silver alloy.
-
Insulate suction line in order to avoid condensation. Liquid line will be insulated only when
exposed to high temperatures (solar radiation, etc.)
-
Horizontal segment of suction line: 4% pitch towards the compressor.
-
In addition to refrigerant, sometimes it’s necessary to add oil. For more than 25 meters,
add 30 grams.
-
When height difference is more than 30 meters, it may be necessary to install an oil
separator on discharge line.
-
If liquid line is descendant and there is a considerable height difference, you have to
compensate the excess pressure before the expansion.
-
If liquid line is ascendant and there is a considerable height difference, the formation of gas
refrigerant before the expansion must be avoided.
-
If you should not find the chosen pipe diameter, you can use the immediately lower
diameter. The system will function normally only with a slight reduction of performance.