9.1.
Programming of the level 0 : LUL.0 – Signal input
Parameter
Affichages
Description / Range
Current input (0/20 mA or 4/20 mA)
Voltage input (0/10 VDC)
PT100 input
Voltage input -5 mV à 56 mV
Input type
Voltage input from 0 mV to 100 mV
Point position (1, 0.1, 0.01, 0.001)
Resolution
(Filter time constant)
Digital filter time constant : for damping the
too fast variations of the signal. 1 to 99
seconds (or OFF). If you notice the "noise" in
the signal, increase this value.
(Display update rate)
Display update rate (0.5 to 6.0 sec).
Zero offset from -200 to +200). (To re-adjust
the measurement for example)
Number of scaling points for linearization.
For a simple straight line, leave 2
Display value scaling point 0 (low).
(mA) Input value scaling point 0 (low).
Display value scaling point 1 (high)
(mA) Input value scaling point 1 (high)
Note : For SCLP > 2, the other points are (DSC2,ISC2), (DSC3,ISC3),…
No reverse
Reverse scaling
Reverse scaling
Set point high limit
Set point low limit
Number of programs
No reset
(RESET)
All parameters set to factory setting
9.2.
Programming of level 1 : LUL.1 – Relay output 1 (idem for LUL.2, 3, 4)
Parameter
Display
Description
Program number
Alarm high limit (mode HA or BAND).
Alarm low limit (en mode LA or BAND).
Alarm hysteresis
RUN P