Input 
(mA)

 

Display 
(digits)

 

ISC0 

4.00

 

ISC1 

20.00

 

DSC1 : 1000 

DSC0 : 0 

 

RSCL = NO 

(No reversal) 

10.2.  Linearization (Scale setting) 

10.2.1  Common case : rectangular tank 2 points 

The  diagram  below  gives  an  example  of  setting  for  a  display  level  0  to  1000  for  an 
input signal from 4.00 to 20.00 mA. 
 
SCLP = 2 
 
Point 0 : 

ISC0 = 04.00 ; DSC0 = 0 

Point 1 : 

ISC1 = 20.00 ; DSC1 = 1000 

 

With ISC1 = 20, DSC1 corresponds to the full scale of the sensor. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Usual scaling : 2 points right lane 

 

It's  possible  to  invert  the  way  of  linearization  in  choosing 
RSCL = YES. In this case, the display will be 1000 for 4.00 mA and 0 
for 20.00 mA. 

 
To display the 

volume of the tank (V), if the heigh (H) is different from the full scale 

of the sensor (PE), enter the following points :  
SCLP = 2 
Point 0 : 

ISC0 = 04.00 ; DSC0 = 0 

Point 1 : 

ISC1 = 20.00 ; DSC1 = (PE x V) / H 

Summary of Contents for ALP842

Page 1: ...s 4 8 Wiring connections 5 9 Programming 6 10 Informations 9 1 General characteristics 1 1 Display 4 digits 7 segments LED RED Height 14mm Messages displayed When the display exceeds 9999 When the display is less than 1999 During initializing the module 3 secondes 4 red LEDs for alarm 1 2 Power supply 24 VDC minimum 20VDC 5VA 1 3 Setting Connection Using the three buttons in front connection by sc...

Page 2: ...een the power supply and other inputs outputs 2000 V Between each relay and other inputs outputs 2000 V 1 12 Weight 300 g 1 13 Conformity EMC normes EN50081 1 EN50082 1 2 Safety Before any intervention be sure to read this entire manual and strictly follow every precaution to ensure the protection of persons required to handle this product Be careful Risk of electric shock 3 Wiring guidelines The ...

Page 3: ...environment not meeting the conditions mentioned in this document Protection against over currents This unit contains no internal fuse The installation of an external fuse 1 A 275 Vac is highly recommended The evacuation of the heat generated by the internal circuitry of the apparatus is effected by the air vents in the electrical housing These vents must not be blocked I O device must be connecte...

Page 4: ... CHAMPLAN Tel 01 69 74 10 90 Fax 01 69 74 10 99 6 Size mm 7 Relay outputs 4 relay outputs have a common point COM Each has a point normally open NO They support loads 5 A 230Vac or 24Vdc Below here s an example of wiring of 4 loads to the mains Side view Top view ...

Page 5: ...230VAC Sensor power supply 4 relay outputs mA V mV V mA Analog output PT100 Rear view terminals Numéro Description L et N Phase and neutral Power supply 230Vac 2 Input signal current mA 3 Input signal voltage V 4 Input signal voltage mV 5 Input signal current or voltage 8 Analog output 9 Analog output 12 Relay 1 Point normally open NO 13 Relay 2 Point normally open NO 14 Relay 3 Point normally ope...

Page 6: ...gram mode press together on for 3 seconds To view next previous function on the same level press on or To increase the value press together on To decrease the value press together on There are several levels of programming LUL 0 to LUL 7 here are the descriptions Level Description LUL 0 Sensor input programming LUL 1 LUL 2 LUL 3 LUL 4 Relay outputs programming LUL 6 Analog output programming LUL 7...

Page 7: ...ue Display update rate Display update rate 0 5 to 6 0 sec Zero offset from 200 to 200 To re adjust the measurement for example Number of scaling points for linearization For a simple straight line leave 2 Display value scaling point 0 low mA Input value scaling point 0 low Display value scaling point 1 high mA Input value scaling point 1 high Note For SCLP 2 the other points are DSC2 ISC2 DSC3 ISC...

Page 8: ...dy value The most common case No alarm relay inactive NO Alarme relay active Relay status No alarm relay active NF Alarme relay inactive Attention In case of power failure the relay is anyway open NO No annunciator Red LED blinking 0 2 seconde Alarm annunciator LED blinking display alarm 9 3 Programming of level 6 LUL 6 Analog output Parameter Display Description Range The copied signal is proport...

Page 9: ... LK 3 LK 4 LK 5 Same parameters Unlilited to parameters of level 6 Read access level 6 LK 6 No access to parameters of level 6 N Do not change nouveau mot de passe Y Change the password New password 0000 à 9999 10 More information 10 1 Option to display alarms Press on to view the status of alarms Press on to see the next alarm Only active alarms are displayed Press on to acquit the displayed alar...

Page 10: ...to 1000 for an input signal from 4 00 to 20 00 mA SCLP 2 Point 0 ISC0 04 00 DSC0 0 Point 1 ISC1 20 00 DSC1 1000 With ISC1 20 DSC1 corresponds to the full scale of the sensor Usual scaling 2 points right lane It s possible to invert the way of linearization in choosing RSCL YES In this case the display will be 1000 for 4 00 mA and 0 for 20 00 mA To display the volume of the tank V if the heigh H is...

Page 11: ...C1 1500 Point 2 ISC2 12 00 DSC2 5000 Point 3 ISC3 14 00 DSC3 8500 Point 4 ISC4 20 00 DSC4 9999 The system will ensure that the curve is increasing That is to say if we look for example DSC2 up above 8500 DSC3 value then DSC3 will also be increased in order to stay on DSC2 least Input mA Display digits ISC0 4 00 ISC1 6 00 ISC2 12 00 ISC3 14 00 ISC4 20 00 DSC4 9999 DSC3 8500 DSC2 5000 DSC1 1500 DSC0...

Reviews: