PMML0600 rev.0 - 06/2022
6
SETTING OF DIP SWIT
CHES AND R
SW SWIT
CHES
ELEC
TRICAL AND C
ONTROL SETTINGS
6.2.1.8 DSW301
◆
Test run mode (Only for RASM-(2/3)VRE)
RASM-(2/3)VRE: PCB2
DSW301
RASM-(2/3)VRE
Factory setting
4
3
2
1
Test run for pump down
4
3
2
1
Not available
4
3
2
1
Not available
4
3
2
1
Not available
4
3
2
1
Forced stoppage of compressor
4
3
2
1
NOTE
•
This operation is reset once the compressor is in Thermo-ON mode.
•
During the test run operation the units will operate continuously during 2 hours without Thermo-
OFF and the 3-minute guard for compressor protection will be effective.
•
Test run will start within 20 seconds after setting DSW1 pin 1 to ON position.
6.2.1.9 DSW302
◆
Optional Function setting (Only for RASM-(2/3)VRE)
RASM-(2/3)VRE: PCB2
DSW302
RASM-(2-3)VRE
Factory setting