TROUBLESHOOTING
(4) Checking Method of Electronic Expansion Valve
(e) By touching the - side of the tester to the L2 terminal
of ACT module and the + side of the tester to the I
terminal of ACT module, measure the resistance.
If all the resistances are greater than 100 k
Ω
, it is
normal.
(f) By touching the + side of the tester to the - terminal
of ACT module and the - side of the tester to the I
terminal of ACT module, measure the resistance.
If all the resistances are less than 100 k
Ω
, it is
normal.
+
-
L2
I
+
-
-
I
+
Indoor Unit Electronic Expansion Valve
Outdoor Unit Electronic Expansion Valve
Locked
Check for the liquid pipe temperature
It is abnormal if the liquid pipe pressure
with
during heating operation.
does not increase during cooling
Fully Closed
It is abnormal if the temperature does
operation.
not increase.
Locked
It is abnormal under the following
It is abnormal if the liquid pipe pressure
with
conditions; The temperature of freeze
does not increase and the outlet
Slightly Open
protection thermistor becomes lower
temperature of the expansion valve
than the suction air temperature when
decreases after the cooling operation
the unit under checking is stopped and
is started.
other units are under cooling operation.
Locked
It is abnormal under the following
with
conditions; After heating operation for
Fully Open
more than 30 min., the discharge gas
temperature of compressor is not 10
o
C
higher than the condensing temperature
and there is no other faults such as
excessive charge of refrigerant, etc.
Unit
Under
Checking
Electronic Expansion Valve
Freeze Protection
Thermistor
Other
Units