1-56
TROUBLESHOOTING
Compressor Pressure/Frequency Indication
Discharge Pressure
(High) (x 0.1 MPa)
20
Suction Pressure
(Low) (x 0.01 MPa)
21
Control Information
22
Operation
Frequency (Hz)
23
Outdoor Unit Code
25
Refrigerant Cycle
Number
26
Refrigerant Cycle
Number
27
Indoor Unit Capacity
24
The current is indicated when compressor is running.
In case of inverter compressor, the running current
of primary side of inverter is indicated.
Capacity Code of Indoor Unit
20
2.5
26
3.0
32
4.0
40
5.0
Indication Code
Equivalent Capacity (HP)
J3: 01 to 16
(01: when shipment (DSW4), Decimal Indication)
J4: 00 to 0F
(00: when shipment (DSW4), Indication with 16 numbers)
In case of Twin Type, it is indicated "P02".
The indication of "255" is normal.
This is an indication for internal information for the remote
control switch. This does not have any specific meaning.
This is an indication for internal information.
This is an indication for internal information.
This is an indication for frequency of inverter.
The capacity of the indoor unit is indicated as shown
in the table below.
Indoor Unit Capacity Indication
Outdoor Unit
Expansion Valve
MV1 Opening (%)
29
Outdoor Unit
Expansion Valve
MV2 Opening (%)
30
Outdoor Unit
Expansion Valve
MVB Opening (%)
31
Indoor Unit
Expansion Valve
Opening (%)
28
Expansion Opening Indication
Compressor
Running Current (A)
32
Estimated Electric Current Indication
Temperature Indication
Returns to Temperature Indication