– 33 –
5. Initial Setting Circuit (IC401)
•
When power is supplied, the microcomputer reads the data in IC401 or IC402 (E
2
PROM) and sets
the preheating activation value and the rating and maximum speed of the compressor, etc. to their
initial values.
•
Data of self-diagnosis mode is stored in IC401 or IC402; data will not be erased even when power is
turned off.
6. Power Supply
First, 35V power which operates the indoor unit is generated by the power source section of the outdoor unit and
supplied to the indoor unit through the C and D lines of the connecting cable.
Second, use the DC/DC converter and the 35 V power supply from the outdoor unit to generate 12 V control
power, which drives the stepping motor during the operation.
In addition, use the regulator IC 121 to generate 5 V power required for driving the micro computer and controlling
fan motor.
If the terminal block was overheated due to a connecting cable improper connection, the thermal fuse built in the
terminal block will burnt to shut off the 12 V line and stop the operation of the indoor unit. Then, the outdoor unit
cannot be communicated with the indoor unit and a communication error occurs (the outdoor LD301 will blink 9
times), stop all operations.
Fig. 6-1
Fig. 5-1
Microcomputer
External ROM
SCL
SDA
0V
0V
0V
5V
5V
5V
C401
IC401 or IC402 (E
2
PROM)
R404
R403
27
26
1
2
3
4
8
7
6
5
}
Summary of Contents for Summit RAC-35YH6
Page 17: ... 15 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAS 35FH6 INDOOR UNIT ...
Page 22: ...RAS 35FH6 CIRCUIT DIAGRAM 20 08A392_05_RAS_35FH6_20 21_A2_E 2008 2 22 18 40 20 ...
Page 25: ... 23 button 25 26 26 27 28 26 RAS 35FH6 08A392_07_RAS_35FH6_23_A3_E 2008 3 7 10 07 23 ...
Page 92: ... 90 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAS 35FH6 ...