Chapter 7
Specifications
7-2
(3) Common specifications of 200 V class and 400 V class models (continued)
Model name (type name)
SJ700D-****FEF3/FUF3
004
L
007
L/H
015
L/H
022
L/H
037
L/H
055
L/H
075
L/H
110
L/H
150
L/H
185
L/H
220
L/H
300
L/H
370
L/H
450
L/H
550
L/H
750
H
900
H
1100
H
1320/1500
H
Inp
ut
Fr
equ
enc
y
se
tt
ing
Standar
d
operator
Setting with
2
1
and
2
1
keys
External
signal
(Note6)
0 to +10 VDC, -10 to +10 VDC (input impedance: 10k
), 4 to 20 mA (input impedance: 100
)
External
port
Setting via RS485 communication
St
ar
t/
st
o
p
c
o
m
m
an
d
Fo
rw
ar
d
/r
ev
e
rs
e
co
m
m
an
d
Standard
operator
Start/stop commands (forward/reverse switching by parameter setting)
External
signal
Forward-operation start/stop commands (reverse-operation start/stop possible when relevant commands are assigned
to intelligent input terminals)
3-wire input possible (when relevant commands are assigned to control circuit terminals)
External
port
Setting via RS485 communication
Intelligent input
terminals
8 terminals, NO/NC switchable, sink logic/source logic switchable
[Terminal functions] Select eight of 69 functions.
Reverse operation (RV), Multispeed 1 setting (CF1), Multispeed 2 setting (CF2), Multispeed 3 setting (CF3), Multispeed 4
setting (CF4), Jogging (JG), external DC braking (DB), 2nd motor control (SET), 2-stage acceleration/deceleration (2CH),
free-run stop (FRS), external trip (EXT), unattended start protection (USP), commercial power supply switching (CS),
software lock (SFT), analog input switching (AT), 3rd motor control (SET3), reset (RS), starting by 3-wire input (STA),
stopping by 3-wire input (STP), forward/reverse switching by 3-wire input (F/R), PID disable (PID), PID integration reset
(PIDC), control gain switching (CAS), acceleration by remote control (UP), deceleration by remote control (DWN), data
clearance by remote control (UDC), forcible operation (OPE), multispeed bit 1 (SF1), multispeed bit 2 (SF2), multispeed bit
3 (SF3), multispeed bit 4 (SF4), multispeed bit 5 (SF5), multispeed bit 6 (SF6), multispeed bit 7 (SF7), overload restriction
selection (OLR), torque limit selection (enabling/disabling) (TL), torque limit 1 (TRQ1), torque limit 2 (TRQ2), P/PI
switching (PPI), LAD cancellation (LAC), trigger for frequency addition (A145) (ADD), forcible-terminal operation (F-TM),
cumulative power clearance (KHC), general-purpose input 1 (MI1), general-purpose input 2 (MI2), general-purpose input
3 (MI3), general-purpose input 4 (MI4), general-purpose input 5 (MI5), general-purpose input 6 (MI6), general-purpose
input 7 (MI7), general-purpose input 8 (MI8), analog command holding (AHD), emergency stop(EMR)*Note4,no
assignment (no)
Thermistor input
terminal
1 terminal (positive temperature coefficient/negative temperature coefficient switchable for resistor)
O
ut
pu
t
Intelligent
output terminals
5 open-collector output terminals, NO/NC switchable, sink logic/source logic switchable
1 relay (1c-contact) output terminal: NO/NC switchable
[Terminal functions] Select six of 51 functions.
Running (RUN), constant-speed reached (FA1), set frequency overreached (FA2), overload notice advance signal (1) (OL),
output deviation for PID control (OD), alarm signal (AL), set frequency reached (FA3), over-torque (OTQ), instantaneous
power failure (IP), under voltage (UV), torque limited (TRQ), operation time over (RNT), plug-in time over (ONT), thermal
alarm signal (THM), 0 Hz detection signal (ZS), set frequency overreached 2 (FA4), set frequency reached 2 (FA5),
overload notice advance signal (2) (OL2), PID feedback comparison (FBV), communication line disconnection (NDc),
logical operation result 1 (LOG1), logical operation result 2 (LOG2), logical operation result 3 (LOG3), logical operation
result 4 (LOG4), logical operation result 5 (LOG5), logical operation result 6 (LOG6), capacitor life warning (WAC),
cooling-fan speed drop (WAF), starting contact signal (FR), heat sink overheat warning (OHF), low-current indication
signal (LOC), general-purpose output 1 (M01), general-purpose output 2 (M02), general-purpose output 3 (M03),
general-purpose output 4 (M04), general-purpose output 5 (M05), general-purpose output 6 (M06), inverter ready
(IRDY), forward rotation (FWR), reverse rotation (RVR), major failure (MJA), alarm code 0 to 3 (AC0 to AC3)
Intelligent
monitor output
terminals
Analog voltage output(Note7), analog current output(Note7), pulse-string output
(e.g., A-F, D-F [n-fold, pulse output only], A, T, V, P)
Monitoring on
display
Output frequency, output current, output torque, frequency conversion data, trip history,
input/output terminal status, electric power, and others
DC braking
Triggered at motor start-up, when the actual motor frequency exceeds the acceleration frequency set by a stop
command, when the actual motor frequency exceeds the frequency set by a frequency command,
or by an externally input command (braking force, time, and frequency are variable).
Other functions
Free V/f setting (7 breakpoints), frequency upper/lower limit, jump (center) frequency, acceleration/deceleration
according to characteristic curve, manual torque boost level/breakpoint, energy-saving operation, analog meter
adjustment, start frequency setting, carrier frequency adjustment, electronic thermal function (available also for free
setting), external start/end frequency/frequency rate, analog input selection, retry after trip, restart after instantaneous
power failure, output of various signals, starting with reduced voltage, overload restriction, initial-value setting,
automatic deceleration at power failure, AVR function, fuzzy acceleration/deceleration, online/offline auto-tuning,
high-torque multi-motor operation (sensorless vector control of two motors by one inverter)
Carrier frequency
variation
CT : 0.5 to 15kHz
VT : 0.5 to 12 kHz
CT : 0.5 to 10kHz
VT : 0.5 to 8 kHz
Protective
functions
Overcurrent protection, overvoltage protection, under voltage protection, electronic thermal protection, temperature
error protection, instantaneous power failure protection,
phase loss
input protection, braking-resistor overload
protection, ground-fault current detection at power-on, USP error, external trip, emergency stop trip, CT error,
communication error, option board error, and others