Chapter 4
Explanation of Functions
4-141
(ii) List of registers (frequency settings and trip monitoring)
Register
No.
Function name
Function code R/W
Monitoring and setting items
Data
resolution
0001h
Frequency source setting
F001 (high)
R/W 0 to 40000 (valid when A001 = 03)
0.01 [Hz]
0002h
F001 (low)
R/W
0003h Inverter status A
-
R
0: Initial status, 1: Waiting for Vdc establishment, 2:
Stopping, 3: Running, 4: Free-run stop (FRS), 5:
Jogging, 6: DC braking, 7: Frequency being input, 8:
Retrying operation, 9: Undervoltage (UV),
-
0004h Inverter status B
-
R
0: Stopping, 1: Running, 2: Tripping
-
0005h Inverter status C
-
R
0: ---, 1: Stopping, 2: Decelerating, 3: Constant-speed
operation, 4: Accelerating, 5: Forward rotation, 6:
Reverse rotation, 7: Switching from forward rotation
to reverse rotation, 8: Switching from reverse
rotation to forward rotation, 9: Starting forward
rotation, 10: Starting reverse rotation
-
0006h PID feedback
-
R/W 0 to 10000
0.01 [%]
0007h
to
0010h
(Reserved)
-
R
Inaccessible
-
0011h Trip Counter
d080
R
0 to 65530
1 [time]
0012h Trip monitoring 1 (factor)
d081
R
See the list of inverter trip factors below
-
0013h Trip monitoring 1 (inverter status)
See the list of inverter trip factors below
-
0014h Trip monitoring 1 (frequency) (high)
0 to 40000
0.01 [Hz]
0015h Trip monitoring 1 (frequency (low)
0016h Trip monitoring 1 (current)
Output current at tripping
0.1 A
0017h Trip monitoring 1 (voltage)
DC input voltage at tripping
1 V
0018h Trip monitoring 1 (running time) (high)
Cumulative running time at tripping
1h
0019h Trip monitoring 1 (running time) (low)
001Ah Trip monitoring 1 (power-on time) (high)
Cumulative power-on time at tripping
1h
001Bh Trip monitoring 1 (power-on time) (low)
001Ch Trip monitoring 2 (factor)
d082
R
See the list of inverter trip factors below
-
001Dh Trip monitoring 2 (inverter status)
See the list of inverter trip factors below
-
001Eh Trip monitoring 2 (frequency) (high)
0 to 40000
0.01 [Hz]
001Fh Trip monitoring 2 (frequency (low)
0020h Trip monitoring 2 (current)
Output current at tripping
0.1 A
0021h Trip monitoring 2 (voltage)
DC input voltage at tripping
1 V
0022h Trip monitoring 2 (running time) (high)
Cumulative running time at tripping
1h
0023h Trip monitoring 2 (running time) (low)
0024h Trip monitoring 2 (power-on time) (high)
Cumulative power-on time at tripping
1h
0025h Trip monitoring 2 (power-on time) (low)
0026h Trip monitoring 3 (factor)
d083
R
See the list of inverter trip factors below
-
0027h Trip monitoring 3 (inverter status)
See the list of inverter trip factors below
-
0028h Trip monitoring 3 (frequency) (high)
0 to 40000
0.01 [Hz]
0029h Trip monitoring 3 (frequency (low)
002Ah Trip monitoring 3 (current)
Output current at tripping
0.1 A
002Bh Trip monitoring 3 (voltage)
DC input voltage at tripping
1 V
002Ch Trip monitoring 3 (running time) (high)
Cumulative running time at tripping
1h
002Dh Trip monitoring 3 (running time) (low)
002Eh Trip monitoring 3 (power-on time) (high)
Cumulative power-on time at tripping
1h
002Fh Trip monitoring 3 (power-on time) (low)
0030h Trip monitoring 4 (factor)
d084
R
See the list of inverter trip factors below
-
0031h Trip monitoring 4 (inverter status)
See the list of inverter trip factors below
-
0032h Trip monitoring 4 (frequency) (high)
0 to 40000
0.01 [Hz]
0033h Trip monitoring 4 (frequency (low)
0034h Trip monitoring 4 (current)
Output current at tripping
0.1 A
0035h Trip monitoring 4 (voltage)
DC input voltage at tripping
1 V
0036h Trip monitoring 4 (running time) (high)
Cumulative running time at tripping
1h
0037h Trip monitoring 4 (running time) (low)
0038h Trip monitoring 4 (power-on time) (high)
Cumulative power-on time at tripping
1h
0039h Trip monitoring 4 (power-on time) (low)