![Hitachi SJ P1 Series Safety Function Manual Download Page 36](http://html.mh-extra.com/html/hitachi/sj-p1-series/sj-p1-series_safety-function-manual_142317036.webp)
11-2
Chapter 11
Specification
・
Technical data
11.3 Recommended ferrule
I/O terminal block is a spring-clamp type.
For safe wiring and reliability, it is recommended for the
signal line to use the ferrules of following specification.
* Ferrules with sleeve
Note 1: Supplier: Phoenix contact
Crimping pliers: CRIPMFOX UD 6-4 or
CRIMPFOX ZA 3
11.4 Safety function
The STO function of SJ-P1 is equivalent to the function
listed below.
Function
Standard
STO
(Safe Torque Off)
EN/IEC61800-5-2
Stop category 0
EN 60204-1
11.5 Response time
Item
Time
Response time of STO
10ms max.
Response time of EDM signal
(reference)
20ms max.
Refer to the User’s Guide of SJ-P1 for the detail
information of wiring on the I/O terminal block.
11.6 Safety-related parameters
Parameter
Value
Standard
PL
e
EN ISO 13849-1:2015
CAT.
4
MTTFd
100 years
DCavg
99.8%
SIL
3
IEC61508: 2010
IEC61800-5-2:2016
EN62061:2012
HFT
1
SFF
99.9%
PFH
1.17×10
-9
PFD
1.03×10
-4
11.7 Environmental specification
Ambient
temperature
-10
~
50°C
Storage
temperature
-20
~
65°C
Humidity
20
~
90%RH (No condensation)
Vibration
*1)
5.9m/s
2
(0.6G)
,
10
~
55Hz
*2)
2.94m/s
2
(0.3G)
,
10
~
55Hz
Location
Altitude 1,000m or less
Indoors (No corrosive gasses or dust)
*1) P1-00044-L(P1-004L)~P1-03160-L(P1-550L)/
P1-00041-H(P1-007H)~P1-01800(P1-550H)
*2) P1-03520-L(P1-750L)~P1-04300-L(P1-900L)/
P1-01760-H(P1-750H)~P1-03160-H(P1-1320H)
Wire size
mm
2
(AWG)
Model name of
ferrule
*1
L1 [mm]
L2 [mm]
φd [mm]
φD [mm]
0.25 (24)
AI 0,25-8YE
8
12.5
0.8
2.0
0.34 (22)
AI 0,34-8TQ
8
12.5
0.8
2.0
0.5 (20)
AI 0,5-8WH
8
14
1.1
2.5
0.75 (18)
AI 0,75-8GY
8
14
1.3
2.8