 When bending the pipes, firmly fix the pipe at

     the heat exchanger side.

Insulation

For  Left Side Piping

For Right Side Piping

Contour of  the Unit

  

 

Fig. 5.1 Liquid pipe

 

 Bend the gas pipe at the flexible pipe part.

Insulation

Fig. 5.2  Gas  pipe

11

Contour of the Unit

For Right  side Piping

For  Left Side Piping

0.8/1.0/1.3/1.5

a

b

c

For Rear  Side Piping

For Rear Side Piping 

Model

Small Cover

Right Side Cover

Left Side Cover

108    410   302

(unit:mm)

(1)  Position of piping connection is shown in 
Figure 5.1 and 5.2.
(2)  Piping Direction for the Indoor Unit Three 
directions of piping connection to the indoor 
unit can be performed; to the rear side, the right 
side and the left side of the unit, respectively. 
Therefore, most appropriate piping for a room can 
be selected.

5.2  Piping Connection

Right Side Piping 
Take off the small cover from right side.

Left Side Piping
Take off the small cover from left side.

Rear Side Piping
Bend pipe backwards directly.

1.8/2.0/2.3

121    415   294

0.8/1.0/1.3/1.5

a

b

c

Model

108    480   372

(unit:mm)

1.8/2.0/2.3

137    484   347

Summary of Contents for RPK-0.8FSNQS

Page 1: ...RPK 0 8FSNQS P00611Q ORIGINAL INSTRUCTIONS Wall Mounted RPK 1 0FSNQS RPK 1 3FSNQS RPK 1 5FSNQS Type RPK 1 8FSNQS RPK 2 0FSNQS RPK 2 3FSNQS ...

Page 2: ...32DB 23WB HITACHI HITACHI HITACHI ...

Page 3: ...es To prevent possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use the return and collection systems or contact the retailer where the product was purchased They can take this product for environmental safe recycling ...

Page 4: ...1 10 10 12 Section2 Installation Maintenance Manual Remote Control Switch Method Setting of Swing Louver Filter Cleaning Taking Out the Filter Cleaning the Filter Reset of Filter Indication 4 5 5 5 5 5 5 5 1 1 2 3 3 3 4 4 ...

Page 5: ...3 17 13 14 14 15 15 16 16 Common 18 the Filter Indication Interval ...

Page 6: ...ental capabilities or lack Children should be supervised that they do not play with the appliance The appliance should not be installed in the laundry of experience and knowledge unless they have been given supervision or instruction concerning use of the 10 Btu h 3 2 0 1 8 2 3 appliance by a person responsible for their safety ...

Page 7: ...Press switches only with fingers Do not press switches by any other item as it may break switches ...

Page 8: ...Regarding the instructions of Wired Remote Control Switch or Wireless Remote Control Switch read the operation manual attached to the control switch ...

Page 9: ...7 8 4 8 1 ...

Page 10: ...9 9 1 9 2 9 3 9 4 5 8 2 8 3 approximately ...

Page 11: ...6 2 Necessary Tools and Instrument List for Installation equipments for R410A Users can not change power lines by themselves replaced by professional maintenance staffs ...

Page 12: ...r Mounting Bracket For Drain Hose Setting Fig 4 1 Operation and Maintenance Space Fig 4 2 Hole for Piping on the Wall 7 For Refrigerant Pipe Thermal Insulation Pipe 11 1 1 1 h DOO 2 to 5mm Diameter of 65mm Hole for Piping 1 225 81 7 2 3 100 150 100 1000 unit mm wall and board hanging ...

Page 13: ... 30 20 25 20 25 20 25 50 25 20 25 20 25 20 8 15 35 28 7 5 34 20 27 20 24 20 20 37 44 150 100 20 20 for Pipe and Wiring ROH Service Space Outline of the Unit Flange Part for Inserting Unit Exterior Contour Suspension Bracket 100 Capacity HP 0 8 1 0 1 3 1 5 unit mm Drain hose Drain hose 217 620 310 125 125 41 41 289 32 65 390 800 1050 80 18 40 40 10 65 695 Capacity HP 1 8 2 0 2 3 unit mm ...

Page 14: ...he unit is completely hooked onto the mounting bracket If not it may drop from the bracket resulting in a serious accident 4 3 3 Removing Front Panel In order to connect the refrigerant piping wiring and to check drain water flow removing the front panel is needed Perform these work according to the following instructions Pay attention to the resin components not to scratch 1 Hold both sides of th...

Page 15: ...e two joints of the front panel back into the grid and then push inside to make the two one tightly fasten 2 Press front panel down make the two joints of the front panel tightly fasten 5 1 Piping Materials 1 Prepare locally supplied copper pipes 2 Select the piping size from the following table 3 Select clean copper pipes making sure there is no dust and moisture inside the tubes Before connectin...

Page 16: ...ver 108 410 302 unit mm 1 Position of piping connection is shown in Figure 5 1 and 5 2 2 Piping Direction for the Indoor Unit Three directions of piping connection to the indoor unit can be performed to the rear side the right side and the left side of the unit respectively Therefore most appropriate piping for a room can be selected 5 2 Piping Connection Right Side Piping Take off the small cover...

Page 17: ... side 3 For 0 8 1 5 when the left side drain piping conection is performed remove the cap of left side drain pipe and then attach this cap to the right side drain pipe in order to change drain piping connection from right side to left side 115 560 45 Contour of the Unit Drain Pipe Connection for Vinyl Pipe VP16 65 Hole for Rear Side Connection for Wiring and Piping Fig 6 2 1 8 2 3 Direction of Dra...

Page 18: ...r into the drain pan and check to ensure that water can flow smoothly Do notconnect thedrain pipeswith sanitary or sewage or any other When installing the pipe do not tie the drain pipe andrefrigerant pipetogether Pay attention to the thickness of the insulation when the left side piping is too thick piping drainage pipe performed If it is cannot beinstalled inthe unit l Tighten screws according t...

Page 19: ...for operating line of the terminal box 2 Use shielded twist pair cable for control cable between outdoor unit and indoor unit control cable between indoor units and remote control switch cable ofPC AR Install a multi pole main switch with a space of 3 5mm or more between each phase 3 The power supply and earth wires have been connected in the factory Please connect to the power circuit with a ELB ...

Page 20: ...Cut Out Cut In For ControlCircuit Fuse Capacity Freeze Protection Thermostat Thermostat Differential 0 8 2 3 15 A 5 0 14 2 Model Indoor Unit ...

Page 21: ...e above table are selected at the maximum current of the unit according to the European Standard EN60335 1 Use the wires which are not lighter than the ordinary polyvinyl chloride sheathed flexible cord code designation H05VV F 220 240V 2 50Hz 220V 60Hz 88t v b b a a a a t t bt bt b a t a t a t a t a a a t Rated current of appliance Nominal cross sectional area 1 5 1 8 2 3 0 40A ...

Page 22: ...eld the unit can not be operated 1 Control Model Setting SW1 In case of using the wired remote control PC ARE and the receiver kit PC ALHZ Setting before shipment is Wireless Set the SW1 of the receiver kit to Wired If not the operation is not available Connect the cables to A B at the terminal board TB2 2 Unit No Setting RSW DSW6 Setting is required Set the unit No of all indoor units respectivel...

Page 23: ...o the holding bracket Write down the contents of the setting on the label The relation between the indication and the interval is shown in the table below COOL HIGH A C SERVICE SET TEMP 01 Flashing Press or switch COOL HIGH A C SERVICE RN ADDS 2 3 Press or switch Press CHECK switch 1 1 Press TIME or switch 2 Press CHECK switch COOL HIGH A C SERVICE Press CHECK switch NOTE Step 2 Selection of Indoo...

Page 24: ...Qingdao Hisense Hitachi Air Conditioning Systems Co LTD P00611Q 2013 10 V00 ...

Reviews: