4.2 Initial Check

4.3 Installation

4.3.1 Suspension Bolts

Install the indoor unit in a space for easy operation

 

and maintenance as shown in Fig. 4.1. 

(1) Select appropriate location and direction for 

installation, and pay careful  attention to the space for

 

the piping, wiring and  maintenance.   

(2) Cut out the area for the indoor unit in the false ceiling 

Fig. 4.1 Space around Indoor Unit

The indoor unit must be installed at an appropriate

location so that the indoor temperature can be evenly

distributed.

There should be no obstruction of air flow at the vent.

         2

and install suspension bolts, as shown in Fig. 4.2.

Back

Front

Electric Box

Service Access (≥450)

Top View

Models 0.8~2.5

1.

Where the ceiling 

is

 

not

 

removable, 

please

 

arrange a 

necessary

 

service 

access under

 

the 

indoor unit.

2.

The service access

shall be so 

arranged

 

that the 

electric box

 

cover/

internal

components can be

removed/repaired 

in

 

a convenient 

manner.

600 Min.

100

10

00

 M

in

.

140

600

60

0

10

00

 M

in

.

To avoid any corrosive action to the heat exchangers, 

do not install the indoor unit in an acid or alkaline 

environment.

Do not install the indoor unit in a machinery shop or

kitchen where vapor from oil or its mist flows to the

indoor unit.

Once the oil deposits on the heat exchanger, it may

impair the performance of indoor unit and cause

damage to plastic parts therein.

Pay attention to the following points when the indoor

unit is installed in a hospital or other facilities where

there are electronic waves from medical equipment,

 

etc.

(A) Do not install the indoor unit where the

electromagnetic wave is directly radiated to the   

electrical box,  remote control cable or remote  

control.

(B) Install the indoor unit and components as far as 

practical or at least 3 meters from the

 electromagnetic 

wave radiator.

 

(C) Install the remote control switch in an iron box. 

Arrange the remote control cable in an iron

 

tube. Ground the iron box and iron tube.

(D) Install a noise filter when the power supply emits 

 harmful noises.

 Fig. 4.2 Mounting the Suspension Bolts

For Concrete Slab

For Steel Beam

150 to 160mm

Screw in

(100 to 150kg)

Concrete

Suspension Bolt

(W3/8 or M10)

Fixing Point

I Beam

Suspension Bolt

(W3/8 or M10)

For Wooden Beam 

Suspension 

Wooden Rib

(60mm to 90mm 

lumber)

Wooden Beam

Nut

Square Washer

Suspension Bolt

Nut

Square Washer

Summary of Contents for RPIZ-0.8HNATNQ

Page 1: ...door unit Please read this manual in conjunction with corresponding manual for outdoor unit RPIZ 0 8HNATNQ RPIZ 1 0HNATNQ RPIZ 1 3HNATNQ RPIZ 1 5HNATNQ RPIZ 1 8HNATNQ RPIZ 2 0HNATNQ RPIZ 2 3HNATNQ RPIZ 2 5HNATNQ Models 0 8 1 3 Model 1 5 Models 1 8 2 5 P01588Q ORIGINAL INSTRUCTIONS ...

Page 2: ......

Page 3: ...cordance with our instructions following the provisions of Directives as amended Manufacturing number and manufacturing year refer to model Nameplate Notes This declaration becomes invalid if technical or operational modifications are introduced without the manufacturers consent Johnson Controls Inc is authorised to Compile the Technical Construction File Ad Westendhof 3 45143 Essen Germany Name S...

Page 4: ...spective signal words Temperature Do not have the air outlet directly faced towards animals or plants since this may bring about an adverse effect thereon The installation and service engineering have to comply with local standards laws and regulations As an appliance inaccessible to the public the installation height of indoor unit of the air conditioner shall be at least 2 5m This air conditione...

Page 5: ...y cause a fire Make sure the air conditioner is installed with enough strength of fixation otherwise the air conditioner may fall or topple over which may bring about machine damage or personal injury Please follow the installation instructions and related regulations and standards for electrical construction otherwise electrical failure or fire may occur due to inadequate capacity or inconsistent...

Page 6: ...immediately with the shipping company Check the model number electrical parameters power supply voltage and frequency and accessories to determine if they are correct Please contact your local dealer in case of problem Our company shall not be held responsible for any consequence arising from the modification to equipment without our written consent Ⅲ ...

Page 7: ...ing Materials 5 2 Piping Connection 8 Test Run 9 Protection and Control Devices 10 Field Operation Electrical Wiring 7 1 General Check 7 2 Wiring 7 3 Field Wire Size for Power Source Line 4 4 5 6 9 9 10 10 2 4 5 6 Drain Pipe Tools Instruments for Installation Transportation Handling 3 1 Transportation 3 2 Handling of Indoor Unit 3 7 10 1 Setting of DIP Switch 10 2 Setting of Fan Speed 10 8 ...

Page 8: ...re etc may occur Be careful not to cause damage to insulation materials of the unit surface when it s lifted 2 Tools Instruments for Installation 4 Installation of Indoor Unit Do not install the indoor unit in a flammable environment since this may cause fire or an explosion 4 1 Factory Supplied Accessories Check to ensure that the following accessories are packed with indoor unit Please refer to ...

Page 9: ... in an acid or alkaline environment Do not install the indoor unit in a machinery shop or kitchen where vapor from oil or its mist flows to the indoor unit Once the oil deposits on the heat exchanger it may impair the performance of indoor unit and cause damage to plastic parts therein Pay attention to the following points when the indoor unit is installed in a hospital or other facilities where t...

Page 10: ... 8 2 5 Outgoing Direction Top View Indoor Unit Capacity HP 1 5 1 8 2 5 b a 950 1220 910 1180 mm Fig 4 3 Suspension Bolt 0 8 1 3 740 700 410 Dimensions of Suspension Bolt a Dimensions of Suspension Bolt b 447 25 8 Fig 4 4 Installation of Indoor Unit Suspension Bolt 4 M10 or W3 8 Field Supplied Nut and Washer 4 M10 or W3 8 Field Supplied 1 Install suspension bolts and nuts Mount nuts to the four bol...

Page 11: ... placement of indoor unit Fig 4 6 Handling Method 4 3 4 Leveling of Indoor Unit 1 Check to ensure the top surface is level and measure the max top surface inclination degree Fig 4 7 Top Surface Inclination Degree 2 As shown in Fig 4 7 the rear part of indoor unit is slightly lower than its front part by 0 5mm so as to facilitate drainage 3 Tighten the suspension nut upon completion of adjustment I...

Page 12: ... Correct Incorrect Blocked with Tape or Plug 4 Discharging and Charging Refrigerant Follow the Installation Maintenance Manual for outdoor unit Excessive and inadequate refrigerant is a leading cause of system anomaly Please inject the right amount of refrigerant Pipe Size Tightening Torque N m 20 40 60 80 Φ15 88 Φ12 7 Φ9 53 Φ6 35 Outside Diameter of Piping a Outside Diameter of Flaring D R22 R407...

Page 13: ...t must be higher than the main Select drain pipes in ample size depending on the refrigerating capacity and quantity of indoor units 4 Check if water flows without obstruction following the procedure shown below after the proper connection of wires and drain pipes Drain Pipe 1 The position of the drain pipe connection is shown in Fig 6 1 2 Prepare a polyvinyl chloride pipe with a 32mm outer diamet...

Page 14: ...al box with wire tie Tighten screws to the following torques The electrical wiring connection for indoor unit is shown in Fig 7 1 1 Connect the remote control wire to the PCB in electrical box through the connection hole on electrical box 2 Connect the power supply and earth wires to the terminals in the electrical box 3 Connect the wires between the indoor unit and the outdoor unit to the termina...

Page 15: ...from copper conductor 5 The wiring specifications for weak current communication circuit shall not be lower than that for RVV S P shielded wires or equivalent and the shielding layer shall be grounded 6 A switch that can ensure all pole disconnection shall be installed between power supply and air conditioning unit in such a manner that the contact spacing shall not be less than 3mm 7 Once the pow...

Page 16: ...C Check to ensure the switch on main power source has been ON for more than 4 hours to warm the compressor by heater Pay attention to the following items while the system is running A Do not touch any of the parts by hand at the discharge gas side since the temperatures of compressor chamber and the pipes at the discharge side are higher than 90 C B Do not push the button of the AC contactor It wi...

Page 17: ...tion Note Symbol indicates the location of DIP switch The position indicated in the diagram is in the factory set state The power supply shall be turned off before the setup of DIP switch Otherwise the settings will be invalid 10 RSW1 RSW2 DSW6 DSW5 DSW4 DSW7 DSW3 Setting of Indoor Unit DSW6 tens digit RSW1 units digit Setting position Insert a flat head screw driver into the slot for setup Ex Set...

Page 18: ......

Page 19: ...P01588Q 2018 08 V00 Qingdao Hisense Hitachi Air conditioning Systems Co Ltd Add 218 Qianwangang Road Economic Technical Development Zone Qingdao P R China 1110023 ...

Reviews: