Refrigerant R410A is non-flammable, non-toxic, and odorless, and may produce toxic gases when exposed to

 

open

flame.  Since  this  refrigerant  gas  is  heavier  than  air,  it  may  result  in  lack  of  oxygen,  thereby  leading  to

 

breathing

difficulties  when  the  area  near  the  ground  is  filled  with  this  gas.  If  that's  the  case,  please  turn  off  the

 

main  switch

immediately, cut off the power supply, and open the doors and windows for ventilation. Put out any

 

open flame, and

contact  your  service  dealer.  Performing  leak  detection  and  gas  tightness  test  with  oxygen,

 

acetylene  or  other

flammable and toxic gases may cause explosion, so nitrogen is recommended for this test.

The standards for safe refrigerant leakage in construction and system operation are determined based on local

regulations or standards.

Use ELB with medium or higher sensing speed (ELB with an operating time of 0.1 seconds or less), or

 

electric

shock or fire may arise.

For installation, the refrigerant piping must be firmly connected before the operation of compressor. For repair,

 

the

refrigerant piping must be moved, handled and removed after the stop of compressor.

Please don't short-circuit the protective device (e.g., the pressure switch, etc.) during operation, since this

 

may

cause fire or explosion.

Do not use any sprays such as insecticide, lacquer, hair spray or other flammable gases within approximately one (1) 

meter from the system.

If the earth leakage breaker (ELB) is frequently activated, please stop the system and contact your local dealer or 

customer services.

Make sure the ground wire is securely connected. The improper grounding of machine may lead to electrical failure. 

Please don't connect the ground wire to gas pipes, tap water pipes, lightning rods or phone ground wires.

Make sure there are no flammable materials around during brazing operation. Please wear leather gloves to prevent 

frostbite when filling refrigerant.

Prevent rats or other small animals damaging the wiring and electrical components. Bitten unprotected parts may 

cause a fire.

Firmly fix the connection wires. The external force of terminal may result in looseness of terminal that may cause a 

fire.

Make sure the air conditioner is installed with enough strength of fixation; otherwise, the air conditioner may fall or 

topple over, which may bring about machine damage or personal injury.

Please follow the installation instructions and related regulations and standards for electrical construction; otherwise, 

electrical failure or fire may occur due to inadequate capacity or inconsistent specifications. 

Never fail to use specified wiring and select correct wiring, since failure to do so may cause electrical failure or fire.

 

Please make sure the outdoor unit is not covered with snow  or ice before use.

This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or 

mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning 

use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. 

Cleaning and user maintenance shall not be made by children without supervision.

The A-weighted emission sound pressure don

'

t exceed 70 dB(A) .

This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or 

mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning 

use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance

Cleaning and user maintenance shall not be made by children without supervision.

本空调维修保养只能由专业人员进行。 

Please don't perform installation works such as refrigerant piping connection, drain pipe connection, and wiring 

connection. Violations may result in system leakage, electrical failure or fire. In the case of fire, please turn off the 

power immediately; please don't touch electrical parts with the hands, or electric shock may arise. 

Do not pour water into the indoor or outdoor unit. This machine is an electric product that may develop serious 

electric failure when exposed to water.

Do not open the service cover of indoor or outdoor units without turning OFF the main power supply; otherwise, this 

may bring about serious safety accident.

Do not touch or adjust safety devices inside the indoor or outdoor units. If they are touched or readjusted, serious 

accident may arise.

DANGER

WARNING 

 


Summary of Contents for RPIZ-0.8HNATNQ

Page 1: ...door unit Please read this manual in conjunction with corresponding manual for outdoor unit RPIZ 0 8HNATNQ RPIZ 1 0HNATNQ RPIZ 1 3HNATNQ RPIZ 1 5HNATNQ RPIZ 1 8HNATNQ RPIZ 2 0HNATNQ RPIZ 2 3HNATNQ RPIZ 2 5HNATNQ Models 0 8 1 3 Model 1 5 Models 1 8 2 5 P01588Q ORIGINAL INSTRUCTIONS ...

Page 2: ......

Page 3: ...cordance with our instructions following the provisions of Directives as amended Manufacturing number and manufacturing year refer to model Nameplate Notes This declaration becomes invalid if technical or operational modifications are introduced without the manufacturers consent Johnson Controls Inc is authorised to Compile the Technical Construction File Ad Westendhof 3 45143 Essen Germany Name S...

Page 4: ...spective signal words Temperature Do not have the air outlet directly faced towards animals or plants since this may bring about an adverse effect thereon The installation and service engineering have to comply with local standards laws and regulations As an appliance inaccessible to the public the installation height of indoor unit of the air conditioner shall be at least 2 5m This air conditione...

Page 5: ...y cause a fire Make sure the air conditioner is installed with enough strength of fixation otherwise the air conditioner may fall or topple over which may bring about machine damage or personal injury Please follow the installation instructions and related regulations and standards for electrical construction otherwise electrical failure or fire may occur due to inadequate capacity or inconsistent...

Page 6: ...immediately with the shipping company Check the model number electrical parameters power supply voltage and frequency and accessories to determine if they are correct Please contact your local dealer in case of problem Our company shall not be held responsible for any consequence arising from the modification to equipment without our written consent Ⅲ ...

Page 7: ...ing Materials 5 2 Piping Connection 8 Test Run 9 Protection and Control Devices 10 Field Operation Electrical Wiring 7 1 General Check 7 2 Wiring 7 3 Field Wire Size for Power Source Line 4 4 5 6 9 9 10 10 2 4 5 6 Drain Pipe Tools Instruments for Installation Transportation Handling 3 1 Transportation 3 2 Handling of Indoor Unit 3 7 10 1 Setting of DIP Switch 10 2 Setting of Fan Speed 10 8 ...

Page 8: ...re etc may occur Be careful not to cause damage to insulation materials of the unit surface when it s lifted 2 Tools Instruments for Installation 4 Installation of Indoor Unit Do not install the indoor unit in a flammable environment since this may cause fire or an explosion 4 1 Factory Supplied Accessories Check to ensure that the following accessories are packed with indoor unit Please refer to ...

Page 9: ... in an acid or alkaline environment Do not install the indoor unit in a machinery shop or kitchen where vapor from oil or its mist flows to the indoor unit Once the oil deposits on the heat exchanger it may impair the performance of indoor unit and cause damage to plastic parts therein Pay attention to the following points when the indoor unit is installed in a hospital or other facilities where t...

Page 10: ... 8 2 5 Outgoing Direction Top View Indoor Unit Capacity HP 1 5 1 8 2 5 b a 950 1220 910 1180 mm Fig 4 3 Suspension Bolt 0 8 1 3 740 700 410 Dimensions of Suspension Bolt a Dimensions of Suspension Bolt b 447 25 8 Fig 4 4 Installation of Indoor Unit Suspension Bolt 4 M10 or W3 8 Field Supplied Nut and Washer 4 M10 or W3 8 Field Supplied 1 Install suspension bolts and nuts Mount nuts to the four bol...

Page 11: ... placement of indoor unit Fig 4 6 Handling Method 4 3 4 Leveling of Indoor Unit 1 Check to ensure the top surface is level and measure the max top surface inclination degree Fig 4 7 Top Surface Inclination Degree 2 As shown in Fig 4 7 the rear part of indoor unit is slightly lower than its front part by 0 5mm so as to facilitate drainage 3 Tighten the suspension nut upon completion of adjustment I...

Page 12: ... Correct Incorrect Blocked with Tape or Plug 4 Discharging and Charging Refrigerant Follow the Installation Maintenance Manual for outdoor unit Excessive and inadequate refrigerant is a leading cause of system anomaly Please inject the right amount of refrigerant Pipe Size Tightening Torque N m 20 40 60 80 Φ15 88 Φ12 7 Φ9 53 Φ6 35 Outside Diameter of Piping a Outside Diameter of Flaring D R22 R407...

Page 13: ...t must be higher than the main Select drain pipes in ample size depending on the refrigerating capacity and quantity of indoor units 4 Check if water flows without obstruction following the procedure shown below after the proper connection of wires and drain pipes Drain Pipe 1 The position of the drain pipe connection is shown in Fig 6 1 2 Prepare a polyvinyl chloride pipe with a 32mm outer diamet...

Page 14: ...al box with wire tie Tighten screws to the following torques The electrical wiring connection for indoor unit is shown in Fig 7 1 1 Connect the remote control wire to the PCB in electrical box through the connection hole on electrical box 2 Connect the power supply and earth wires to the terminals in the electrical box 3 Connect the wires between the indoor unit and the outdoor unit to the termina...

Page 15: ...from copper conductor 5 The wiring specifications for weak current communication circuit shall not be lower than that for RVV S P shielded wires or equivalent and the shielding layer shall be grounded 6 A switch that can ensure all pole disconnection shall be installed between power supply and air conditioning unit in such a manner that the contact spacing shall not be less than 3mm 7 Once the pow...

Page 16: ...C Check to ensure the switch on main power source has been ON for more than 4 hours to warm the compressor by heater Pay attention to the following items while the system is running A Do not touch any of the parts by hand at the discharge gas side since the temperatures of compressor chamber and the pipes at the discharge side are higher than 90 C B Do not push the button of the AC contactor It wi...

Page 17: ...tion Note Symbol indicates the location of DIP switch The position indicated in the diagram is in the factory set state The power supply shall be turned off before the setup of DIP switch Otherwise the settings will be invalid 10 RSW1 RSW2 DSW6 DSW5 DSW4 DSW7 DSW3 Setting of Indoor Unit DSW6 tens digit RSW1 units digit Setting position Insert a flat head screw driver into the slot for setup Ex Set...

Page 18: ......

Page 19: ...P01588Q 2018 08 V00 Qingdao Hisense Hitachi Air conditioning Systems Co Ltd Add 218 Qianwangang Road Economic Technical Development Zone Qingdao P R China 1110023 ...

Reviews: