Select the suitable areas to install the unit with approval of
the user.
•
Ensure that the air path is not blocked.
•
Ensure that condensate can drain properly.
•
Ensure that the ceiling is strong enough to bear the weight of
the indoor unit.
• Ensure the sufficient clearance for maintenance and service.
(See Fig.3.2.1).
•
Piping between the indoor and outdoor units should be
within the allowable limits. (Refer to the installation manual
of the outdoor unit.)
•
The indoor unit, outdoor unit, power supply wiring and
transmission wiring should be at least 1 meter away from
televisions and radio, to prevent interference and noise
in those electrical appliances. (Noise may be generated
depending on the conditions under which the electric wave is
generated, even if one-meter.)
•
Use suspension bolts to install the unit, check whether the
ceiling is strong enough to support the weight of the unit. If
there is a risk that the ceiling is not strong enough, reinforce
the ceiling before installing the unit.
•
If there are 2 units of wireless type, keep them at least 6m
away to avoid malfunction due to cross communication.
•
When plural indoor units are installed nearby, keep them
away for more than 4-5m.
Space for installation and service
4000~5000mm or more
100mm or more
300mm or more
150mm or more
5mm or more
Obstacle
Ceiling installation
4000~5000mm
100mm or more
150mm or more
150mm or more
Floor
150mm or more
Wall
Wall
Floor
Floor standing installation
Fig. 3.2.1
3.3
Installation
According to the actual installation space, installation can be
done in the ceiling or on the floor.
3.3.1 Suspension bolts
1
Consider the pipe direction, wiring and maintenance access
carefully, and choose the proper direction and location for
installation.
2
Install the suspension bolts as shown in Fig. 3.3.1. below.
g
g
g
For concrete
For steel beam
For wooden beam
(W3/8 or M10)
Suspension
bolts
Concrete
150 to 160mm
Screw in
(100 to 150kg)
Steel
bar
Wood rib
(60mm to 90mm)
Wooden beam
“
I
” shaped steel
beam
Suspension bolts
(W3/8 or M10)
Nut
Round washer
Nut
Suspension bolts
Square washer
Fig. 3.3.1 Fixing the suspension bolts
3.3.2 Position of the suspension bolts and
pipes
1
Mark the positions of suspension bolts, refrigerant pipes and
drain pipes.
2
The dimensions are shown below.
17
0
68
0
39
39
A
B
25
0
(Unit: mm)
Blowout opening
Capacity
a
b
3.0HP
990
912
3.5/4.0HP
1285
1207
5.0/6.0/6.5HP
1580
1502
Fig. 3.3.2 Suspension bolts