ENGLISH
3.1 UNIT INSTALLATION
3.1.1
Factory-supplied accessories
Accessory
Q'ty
Purpose
Suspension
bracket
2
For unit
suspension
Fixing Screw
(M4 x 10 mm)
2
Drain Hose
1
Wire Clamp
2
For Seal piping
Insulation
Material (5T x
200 x 200 mm)
1
For Seal piping
Sealing Plate
(0.8 T x 118 x 42
mm)
1
For Sealing
Knockout Hole
3.1.2
Initial check
Install the indoor unit with proper clearance around it for
operation and maintenance working space, as shown below
Min. 40
Min. 300
Min. 300
(mm)
Min.
500
Min. 400
Min. 8
Check down slope pitch of drain piping is following the
specification indicate in chapter 'Drain Piping'
3.1.3
Installation
Mounting suspension bracket
• When installing the indoor unit, use the installation pattern
printed on the inner side of the carton box, cutting the carton
box along dotted lines when unpacking is performed
Dotted line
• Installation pattern is giving the following information:
-
Pintch of sling bolt for case (a) and case (b) showed
below
-
Hole Positions of Refrigerant Piping
-
Hole Positions of Drain Piping
• Suspension bracket has the following two possible positions:
CASE A
CASE B
Unit: mm
Model
A
B
C
D
E
F
RPC-3.0
1314
1140
1230
110
280
235
RPC-4.0
RPC-5.0
1574
1400
1490
110
280
235
RPC-6.0
• Select the suspension bracket system depending of your
needs, for semi-concealed installation we recommend Case
(a)
• Mount the suspension brackets to the slings bolts or anchor
bolt and secure them with nuts (File-Supplied), as shown
below
Indoor unit
rear side
Sling Bolt (M10)
(Field-Supplied)
Suspension
Bracket
Indoor unit
Front side
Nuts and Washers
(Field-Supplied)
?
N O T E
Tighten the nuts of the sling bolts or anchor bolts with the suspension
brackets after the adjustment is completed. Apply Lock-Tight paint to the
bolts and nuts in order to prevent them from loosening.
UNITS INSTALLATION
PMML0320A rev.4 - 08/2016