Outputs from system controller – Configuration 1.2
X1
Heating circuit 1 circulation pump
230 Volts
X2:X3
Heating circuit 1 mixing valve
230 Volts
X4
Heating circuit 2 circulation pump
230 Volts
X5:X6
Heating circuit 2 mixing valve
230 Volts
X7
3 port valve
230 Volts
X8
Heat pump on/off
230 Volts
X9
DHW Immersion heater relay control
NOTE: Do NOT connect the immersion heater to the controller without an
intermediate relay. See below.
230 Volts
DANGER
(External power
source to X9,
Isolate elsewhere)
A1
Heat pump 0 – 20mA control
Extra low voltage
C2
RF Receiver
Extra Low voltage
C3
Heat pump communications signal
Extra Low voltage