The diagrams, connections and settings set out on the following pages provide examples of heating
system layouts and relevant connections to the Advanced System Controller. This information is
provided for guidance only. Detailed system design must always be carried out in order to ensure
correct system operation.
Heating circuit examples - 1
Single circuit unmixed (essential settings)
Parameter
Description
Menu
P101
Heating circuit 1 type 0 (direct)
03>01
P102
HC1 OTC heating curve (set as required for system and building type)
04>01>00
P103
HC1 Heating system emitter type 0= UFH, 1=Radiator, 2=Convector
04>01>01
System Configuration (other settings)
P104
HC1 Room compensation settings
04>01>02
P105, P106
HC1 minimum and maximum supply set-points
04>01>03-04
Inputs to system controller
U1
System supply temperature sensor
(May be on supply to Buffer or in buffer, see configuration options for detail)
Extra Low voltage
Outputs from system controller
X1
Heating circuit 1 circulation pump if not derived from local heating controls
230 Volts