![Hitachi RCI-3.0UFE1NH Service Manual Download Page 27](http://html.mh-extra.com/html/hitachi/rci-3-0ufe1nh/rci-3-0ufe1nh_service-manual_2139382027.webp)
2
.TROUBLESHOOTING
Fault
code
Fault description
Possible
r
eason
s
f
or
a
bnormality
How to
d
eal
w
ith
Remarks
74 Indoor EEPROM
Data 2
fault
EE in MCU is fai
ls
, the unit
can run, but the function user
has set is ineffective.
Replace EE data in MCU.
81
Indoor ambient
Temperature
Sensor Fault
1.
The cable of the room
temperature sensor
is
connect
ed
loose
ly
;
2.
The room temperature sensor
fail
s
;
3.
The sampling circuit is abnormal
.
1. Reconnect the cable of the
room temperature sensor;
2. Replace the room temperature
sensor;
3. Replace the indoor control
board.
83
Evaporator Middle
Temperature
Sensor Fault
1.
The cable of the coil temperature
sensor of the evaporator fail
s
;
2.
The coil temperature sensor of
the evaporator
fail
s
;
3.
The sampling circuit is abnormal
.
1. Reconnect the cable of the
coil temperature sensor of the
evaporator;
2. Replace the coil
temperature sensor of the
evaporator;
3. Replace the indoor
control board.
FE
(254)
Communication
between main
control board &
Wir
ed
controller
Fault (display on
wir
ed
controller)
1. The
wir
ed
controller
and
the
indoor
control board
are
connect
ed
loose
ly
;
2.
The sequence of the wiring
between the wir
ed
controller
to the indoor control board
is
wrong;
3.
The wiring between the
wir
ed
controller to the indoor
control board fail
s
;
4.
The wir
ed
controller
fai
ls
;
5.
The indoor control board
is abnormal.
1.
2.
Reconnect the wiring between
the wir
ed
controller to the
indoor control board;
Replace the wiring between
the wir
ed
controller to the
indoor control board;
3.
Replace the wiring between
the wir
ed
controller to the
indoor control board;
4.
Replace the wir
ed
controller;
5.
Replace the indoor control
b
oard.
ER
Communication
between main
control board
&
display board
Fault (displays on
display board)
1.
The wiring between the display
board to the indoor control
board
is
connect
ed
loose
ly
;
2.
The sequence of the wiring
between the display board to the
indoor control board is wrong;
3.
The wiring between the display
board to the indoor control
board
fail
s
;
4.
The display board
fail
s
;
5.
The indoor control board fail
s
.
1.
Reconnect the
wiring
between
the display board
to the
indoor control board;
2.
Replace the wiring between
the display board to the
indoor control board;
3.
Replace the wiring between
the display board to the
indoor control board;
4.
Replace the display board;
5.
Replace the indoor
control
board.
25