3 Control functions
Anti Legionella function
SMGB0135 rev.0 - 06/2020
21
3
3.5 Anti Legionella function
When anti legionella mode is set, the unit will raise the selected temperature of the tank (between 50 to 75°C) once a
week to sterilize the water.
Anti legionella mode uses the electrical heater.
The
icon appears on the main screen.
It is possible to configure the following parameters:
Status of anti legionella operation
(enabled/disabled)
Specified day for anti legionella operation
Specified time of the day for anti
legionella operation
Setting for domestic hot water
temperature in anti legionella operation.
Between 50 ºC to 75 ºC.
Duration of shock treatment.
Between 10 to 60 minutes.