TC-12001
2-113
OUTDOOR UNIT
P5414950-rev.1
37
Single Type
Term
(measure)
Model
ELB
(A)
Normal Current
of Main Switch
(A)
Fuse Capacity
of Main Switch
(A)
Wiring Capacity (mm
2
)
Power Supply
Between
O.U. and I.U.
Earth
Wiring
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
Power
Source
Cable
Control
Cable
*1
*2
*3
*4
*5
*6
*7
*8
*9
*10
*11
*12
*14
*15
*17
RAS-3HVRNM2
32
5
32
40
5
40
32
5
32
4
0.75
4
0.75
0.75
2.0
RAS-4HVRNM2
50
5
40
60
5
50
50
5
40
10
0.75
6
0.75
0.75
3.5
RAS-5HVRNM2
50
5
40
60
5
50
50
5
40
10
0.75
6
0.75
0.75
3.5
RAS-6HVRNM2
50
5
40
60
5
50
50
5
40
10
0.75
6
0.75
0.75
3.5
RAS-7HVRNM2
50
10
40
60
10
50
50
10
40
10
0.75
6
0.75
0.75
3.5
Twin Type
Term
(measure)
Model
ELB
(A)
Normal Current
of Main Switch
(A)
Fuse Capacity
of Main Switch
(A)
Wiring Capacity (mm
2
)
Power Supply
Between O.U. and I.U.
Between I.U. and I.U.
Earth
Wiring
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
Power
Source
Cable
Control
Cable
Power
Source
Cable
*1
*2
*3
*4
*5
*6
*7
*8
*9
*10
*11
*12
*14
*15
*16
*17
RAS-3HVRNM2
32
5
32
40
5
40
32
5
32
4
0.75
4
0.75
0.75
0.75
2.0
RAS-4HVRNM2
50
5
40
60
5
50
50
5
40
10
0.75
6
0.75
0.75
0.75
3.5
RAS-5HVRNM2
50
5
40
60
5
50
50
5
40
10
0.75
6
0.75
0.75
0.75
3.5
RAS-6HVRNM2
50
5
40
60
5
50
50
5
40
10
0.75
6
0.75
0.75
0.75
3.5
Triple Type
Term
(measure)
Model
ELB
(A)
Normal Current
of Main Switch
(A)
Fuse Capacity
of Main Switch
(A)
Wiring Capacity (mm
2
)
Power Supply
Between O.U. and I.U.
Between I.U. and I.U.
Earth
Wiring
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
Power
Source
Cable
Control
Cable
Power
Source
Cable
*1
*2
*3
*4
*5
*6
*7
*8
*9
*10
*11
*12
*14
*15
*16
*17
RAS-4HVRNM2
50
5
40
60
5
50
50
5
40
10
0.75
6
0.75
0.75
0.75
3.5
RAS-5HVRNM2
50
5
40
60
5
50
50
5
40
10
0.75
6
0.75
0.75
0.75
3.5
RAS-6HVRNM2
50
5
40
60
5
50
50
5
40
10
0.75
6
0.75
0.75
0.75
3.5
Quad Type
Term
(measure)
Model
ELB
(A)
Normal Current
of Main Switch
(A)
Fuse Capacity
of Main Switch
(A)
Wiring Capacity (mm
2
)
Power Supply
Between O.U. and I.U.
Between I.U. and I.U.
Earth
Wiring
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
Power
Source
Cable
Control
Cable
Power
Source
Cable
*1
*2
*3
*4
*5
*6
*7
*8
*9
*10
*11
*12
*14
*15
*16
*17
RAS-4HVRNM2
50
5
40
60
5
50
50
5
40
10
0.75
6
0.75
0.75
0.75
3.5
RAS-5HVRNM2
50
5
40
60
5
50
50
5
40
10
0.75
6
0.75
0.75
0.75
3.5
RAS-6HVRNM2
50
5
40
60
5
50
50
5
40
10
0.75
6
0.75
0.75
0.75
3.5
ELB: Earth Leakage Breaker
I.U.: Indoor Unit
O.U.: Outdoor Unit
Table 7.2 Recommended Wiring Capacity and Size
Summary of Contents for RAS-3HVRNM2